CABLE REQUIREMENTS

Select the proper cable size per Table 9.1 and 9.2.
UPS
Max. DC
Rating
Current
15kVA
64 Adc
20kVA
85 Adc
25kVA
107 Adc
30kVA
128 Adc
50kVA
215 Adc
80kVA
344 Adc
100kVA 430 Adc
28
TABLE 9.1 - 440B TO TB1 DC POWER CABLE SIZES
(
Cable sizes for 75°C Copper Cable)
Recommended Wire size and Torque Requirement
Batt Cab
Lug
MCCB
Capacity
150 A
#8 AWG – 3/0
150 A
#8 AWG – 3/0
150 A
#8 AWG – 3/0
150 A
#8 AWG – 3/0
250 A
(2x) #2 – 600
kcmil
350 A
(2x) #2 – 600
kcmil
400 A
(2x) #2 – 600
kcmil
TABLE 9.2 - 440B TB2 CONTROL WIRE SIZE
Battery Cab
Lug Cable
Capacity
All
22 - 12 AWG
4400 Series UPS Battery Cabinet Installation and Operation Manual – 69445-005
Recommended
Cable Strip
Cable Size
#2 AWG
0.65 in (16 mm)
#2 AWG
0.65 in (16 mm)
#2 AWG
0.65 in (16 mm)
#2 AWG
0.65 in (16 mm)
250 kcmil
1.3 in, (33 mm)
600 kcmil –
1.3 in, (33 mm)
2 x 250 kcmil
2x 350 kcmil
1.3 in, (33 mm)
Screw
Lug Torque
#6
9 lb-in (1.01 N•M)
Tightening
Back
Torque
120 lb-in (14
N•M)
120 lb-in (14
N•M)
120 lb-in (14
N•M)
120 lb-in (14
N•M)
500 lb-in (56
N•M)
500 lb-in (56
N•M)
500 lb-in (56
N•M)