[ IX Test Run Mode ]

[7] Standard Operation Data (Reference Data)

(1) Cooling operation
Ambient
tempera-
ture
Operating
conditions
Piping
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE07150
Operation
Indoor
DB/WB
Outdoor
Main pipe
Branch pipe
m [ft]
Total pipe length
Pulse
MPa
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Accumulator outlet
SCC outlet (TH6)
°C [°F]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
outlet
Outdoor unit model
PUHY-P500YSHM-A
27°C/19°C [81°F/66°F]
35°C/ - [95°F/ - ]
7.5 [24-3/5]
-
7.5 [24-3/5]
A
27.8
V
380
Hz
97
543
94
1400
[psi]
2.98/0.76 [432/110]
92 [198]
38 [100]
13 [55]
13 [55]
20 [68]
20 [68]
44 [111]
20 [68]
15 [59]
- 95 -