TE Series
Table 2.6: TE Series Wire Ranges and Torque Specifications
2.6.1
Connection points for units of 160A and below are saddle clamps
suitable for stranded wire. Connection points for units of 210A and
above are bus tabs with pre-drilled holes (see below). Use appropriate
compression or mechanical lugs for termination to these bus tabs.
Suggested wire sizes and tightening torques for factory-supplied
connectors when using conductors rated for 75°C are shown in the
chart below. Always consult local codes and industry standard practices
for proper wires sizes to accommodate voltage drop and ambient
conditions.
Current
Model
Range
Number
Min.- Max.
TE-18-BP
9 - 18
TE-28-BP
14 - 28
TE-39-BP
19 - 39
TE-48-BP
24 - 48
TE-62-BP
36 - 62
TE-78-BP
39 - 78
TE-92-BP
46 - 92
TE-112-BP
56 - 112
TE-150-BP
75 - 150
TE-160-BP
80 - 160
TE-210-BP or -P
105 - 210
TE-276-BP or -P
138 - 276
TE-360-BP or -P
180 - 360
TE-450-BP or -P
225 - 450
TE-550-BP or -P
275 - 550
TE-718-BP or -P
356 – 718
TE-900-BP or -P
450 – 900
TE-1000-BP or -P
50 - 1000
CF = Consult Factory
2.7
The keypad / operator interface unit can be remotely mounted up to 10'
(3 meters) away from the starter, i.e. on the enclosure door. A remote
mounting kit is necessary, consisting of an adaptor plate, a doorframe
for NEMA 1 or NEMA 12 enclosures and a pre-assembled ribbon cable
available in 1-meter length increments. Detailed assembly instructions
and an enclosure cutout template are included with that kit. See Product
Selection Guide for part numbers of the different kits depending on
NEMA rating and cable lengths.
Remote Keypad Mounting Kit
Digital Solid State Soft Starters 18 – 1250A
Power Terminals:
Suggested
Tightening
Wire Size
Torque
AWG
in.-lbs.
12
10
35
8
6
4
3
45
2
2
0
80
2/0
4/0
300 kCMIL
200
500 kCMIL
2 x 250 kCMIL
2 x 250 kCMIL
CF
CF
CF
CF
CF
CF

Remote Keypad Mounting

~
~
~
Figure 2.7
Components
9
Screw / Bolt
Tightening
Size
Torque
Nm
1 x M5
4
(included)
1 x M8
5
(included)
1 x M8
9
(included)
1 x 0.38" hole
(M10)
for User
15
supplied
lugs
CF
CF
CF
CF
CF
CF
Adaptor Plate
NEMA 1 or
NEMA 12
Door Frame
Ribbon Cable,
1, 2 or 3 meters
Suggested
Wire Size
2
ISOmm
6
10
16
16
25
35
35
50
70
70
120
150
300
2 x 150
2 x 150
CF
CF
CF
TE Starter