Low voltage digital solid state startern 18–1250a
Table of Contents

Advertisement

TE Series
Fn #
Group
F030
F031
F032
F033
F034
F035
F036
F037
F038
F039
Table 5.5.7: Run Timer and Time Clock Controller Function Group
Fn #
Group
F040
F041
F042
F043
F044
F045
F046
F047
Table 5.5.8: Current and Ground Protection Features Group
5.5.7
Function Description
Run Timer Selection
Run Timer Time
for use in F030 above
24hr
Time Clock Controller (TCC)
Start Event Mode.
Chose "One Shot"
or 1 to 7 "Start Events"
from F033 – F039
Run time for this mode comes
from F030 above.
Start Event #1 Start Time
Start Event #2 Start Time
Start Event #3 Start Time
Start Event #4 Start Time
Start Event #5 Start Time
Start Event #6 Start Time
Start Event #7 Start Time
5.5.8
Function Description
Current Imbalance Trip
Current Imbalance Trip Delay
Over Current Trip
Over Current Trip Delay
Under Current Trip
Under Current Trip Delay
Ground Fault Trip
Ground Fault Trip Delay
Digital Solid State Soft Starters 18 – 1250A
Process Timer Features
Adjustment / Display Range
0 = Disabled (No timer operation)
1 = Minimum (Batch) Run Timer
2 = Permissive Run Timer
1-9999 minutes after a Start
Command or Start Event from TCC
Start Event Cycle (SEC) Settings.
1 = Loop SEC every day
nd
2 = Loop SEC every 2
day
rd
3 = Loop SEC every 3
day
th
4 = Loop SEC every 4
day
th
5 = Loop SEC every 5
day
th
6 = Loop SEC every 6
day
7 = Loop SEC one day per week
8 = Single 24hr SEC
(until programmed again)
0 = One Shot: Start Event comes
from Start command only
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
00:00-23:59 (hh:mm) or OFF
Current and Ground Fault Protection Features
Adjustment / Display Range
0 = Disabled, or
5 - 30% imbalance
1 - 20 seconds
0 = Disabled, or
100 - 300% of motor FLA
1 - 20 seconds
0 = Disabled, or
10 - 90% of motor FLA
1 - 60 seconds
0 = Disabled, or
5 - 90% of CT ratio from Fn 74
1 - 60 seconds
32
Setting
Factory
Section
Increments
Setting
0
1
Disabled
1
1
0
1
One Shot
Append.
1
OFF
1
OFF
1
OFF
1
OFF
1
OFF
1
OFF
1
OFF
Setting
Factory
Section
Increments
Setting
0
1%
Disabled
2
1 second
seconds
0
1%
Disabled
1 second
1 second
0
1%
Disabled
2
1 second
seconds
0
1%
Disabled
2
1 second
seconds
5.6.7
and
4
5.6.8

Hide quick links: