Panasonic PAW-160MAH2L Installation Instructions Manual page 61

Air handling unit kit for panasonic ecoi; panasonic eco g; panasonic paci
Table of Contents

Advertisement

Section C
Connections
No.
10
9
8
7
6
5
4
3
2
1
Section D
Connections
No.
10
9
8
7
6
5
4
3
2
1
Section E
Connections
No.
10
9
8
7
6
5
4
3
2
1
To be continued on next page.
Name
In / Out
Allocation
ON6
O
Recirculat. Operation
ON5
O
Heating Operation
ON4
O
Cooling Operation
ON3
O
Thermostat ON
ON2
O
Defrost Operation
Potential for ON2
ON1
O
to ON6 (12 V DC)
COM
I
Potential for DI1 to DI3
DI3
I
Digital Input 3
DI2
I
Digital Input 2
DI1
I
Digital Input 1
Name
In / Out
Allocation
BLIND
Unused
HU2
O
No polarity
HU1
O
No polarity
2Z-7
I
Potential for OP3
OP3
I
Fan Alarm
1Z-3
O
No polarity
1Z-5
O
No polarity
I
Protective earth
N
I
Neutral
L
I
Live
Name
In / Out
Allocation
M1-6
I
WHT
M1-5
I
GRY
M1-4
I
BLK
M1-3
I
YEL
M1-3
I
RED
M1-1
I
ORG
R2
I
No polarity
R1
I
No polarity
U2 (OC)
I
No polarity
U1 (OC)
I
No polarity
Electrical Wiring
Function
Comment
Status Outputs
Internal Potential: 12 V DC
2 types of usage:
Digital Inputs
a) Potential-free:
(For information on functionality
refer to section "Terminal layout –
CZ-CAPBC2 / ACC-SP1A" in this
b) 12 to 24 V DC, 10 mA external:
document)
Function
Comment
Internal Potential:
External Humidifi er Control
230 V AC / max. 3 A
Fan Alarm Input
(Unit will only operate if this contact is
Internal Potential: 230 V AC
closed, otherwise error code P01 will
be displayed.)
External Potential:
Fan Start – Stop Signal
max. 230 V AC / 5 A
Protective Earth Conductor
Neutral Terminal
External Potential:
Live Terminal
230 V AC, max. 1 A
Function
Comment
Required only for PAW-160MAH2(L/M)
and PAW-280MAH2(L/M)
Expansion valve
(only ECOi and ECO G)
Terminal for Group Wiring
Internal Potential: 16 V DC
(RC connection)
Communication bus wiring
Keep S3 of CZ-CAPBC 2/
ACC-SP1A on "NON VOLTAGE".
Change S3 of CZ-CAPBC2 /
ACC-SP1A to "VOLTAGE".
59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents