Mitsubishi Electric 700 Series Instruction Manual page 14

Plug-in option
Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

REMARKS
• Information on blade terminals
Commercially available product examples (as of March 2008)
Wire Size
Terminal
Screw Size
(mm
M2
0.3, 0.5
Blade terminal crimping tool: CRIMPFOX ZA3 (Phoenix Contact Co., Ltd.)
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is
inappropriate, or the face is damaged.
(1) Loosen the terminal screw and insert the cable into the terminal.
Screw Size
Tightening Torque
M2
0.22N⋅m to 0.25N⋅m
CAUTION
• Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or
malfunction due to damage to the screw or unit.
INSTALLATION AND WIRING (FR-A700/F700 SERIES)
Blade Terminal Model
2
With insulation sleeve
)
AI 0,5-6WH
Damaged
0.3mm
Without insulation sleeve
A 0,5-6
Unstranded
wires
Wires are not inserted
into the shell
Crumpled tip
Cable Size
Small
2
2
to 0.75mm
(Tip thickness: 0.4mm/tip width: 2.5mm )
Maker
Phoenix Contact
Co.,Ltd.
Screwdriver
flat-blade screwdriver
2
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a7axFr-a7ax e

Table of Contents