TOSHIBA SYNC KIT INSTALLATION MANUAL 480/480 V 500/750 kVA Document: 200153-001 Ref: 4GBH0112 Rev. B March 2020...
Page 3
UNINTERRUPTIBLE POWER SYSTEM If additional information or technical assistance is required call TOSHIBA Customer Support Center at 877-867-8773, or write to: Toshiba International Corporation, 13131 West Little York Road, Houston, TX 77041-9990 Attn: UPS Product Manager.
Page 4
TOSHIBA shall not be liable for technical or editorial omissions or mistakes in this manual. Nor shall it be liable for incidental or consequential damages resulting from the use of information contained in this manual.
Prohibit: A prohibit symbol shows the act the user or the service personnel should NEVER perform during the UPS installation, operation or service work. PROHIBIT Safety Recommendations: If any problems are encountered while following this manual, contact the Toshiba Customer Support Center. G2020 TOSHIBA SYNC KIT Installation Manual - 200153-001...
Be trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses, face shield, flash clothing, etc. in accordance with established practices Be trained in rendering first aid. G2020 TOSHIBA SYNC KIT Installation Manual - 200153-001...
Each TOSHIBA SYNC KIT contains all hardware necessary for one pair of master and slave UPS to operate in a synchronous configuration. Each additional UPS unit will require another sync kit, if applicable. This manual contains kit installation and startup information specifically for the G2020 Series UPS.
Field-installed wirings * Use part No.14 for the cover plate. Two (3) screws (M4) with spring washer and flat washer for connection Figure 5-1: Installation Procedure for MASTER UPS G2020 TOSHIBA SYNC KIT Installation Manual - 200153-001...
10. Connect the field-installed wirings (from MASTER UPS) to the Fuse holder. 11. Attach the cover plate using (2) screws (M5) on the Metallic Plate. 12. Connect the Jumper wiring between the terminal 13 and 14 of TN1 on IO1 PCB (IOAU-09*). G2020 TOSHIBA SYNC KIT Installation Manual - 200153-001...
* Use part No.14 UN - V One (1) screw (M4) with VN - W spring washer and flat washer WN - U for grounding. Figure 6-2: Installation procedure for SLAVE UPS (2) G2020 TOSHIBA SYNC KIT Installation Manual - 200153-001...
Initialize converter operation; Initialize inverter operation; After initialization, LCD screen should appear. (Refer to the G2020 series service manual, 5-1 Start-up Procedure for details.) 2. Press the "MAINT" button located on the SW1 PCB (DPAU-81*). Maintenance screen will appear. 3. Press the "SETUP" tab on the Maintenance screen, and then press the "INPUT PORT" button.
Verify Proper Setup To confirm that the TOSHIBA SYNC circuit is functioning properly, during TOSHIBA SYNC operation, “Ath Bus Sync.” is displayed at the bottom of LCD screen as shown in Figure 8-1. Figure 8-1: Example of TOSHIBA SYNC operation display...