G9000 SERIES MMS KIT INSTALLATION MANUAL 480/480 V 1000/1330/1500/1660/2000kVA Document No.: 200150-001 Document: 4GBH0153 Rev. B March 2020...
Page 3
If additional information or technical assistance is required call TOSHIBA Customer Support Center at 8773, or write to: Toshiba International Corporation, 13131 West Little York Road, Houston, TX 77041-9990 Attn: UPS Product Manager. Keep this manual with the UPS equipment.
Page 4
TOSHIBA shall not be liable for technical or editorial omissions or mistakes in this manual. Nor shall it be liable for incidental or consequential damages resulting from the use of information contained in this manual.
Table of Contents Table of Contents ................................iii List of Tables ..................................iii List of Figures ..................................iii How to use this Manual ............................... 1 Notice Icons ................................. 1 Qualified Personnel ............................. 2 OVERVIEW ................................. 3 MMS KIT Parts List ..............................4 Installation Procedures ..............................
Page 6
This Page Left Intentionally Blank G9000 MMS KIT Installation Manual 1000-2000kVA – 200150-001...
Prohibit: A prohibit symbol shows the act the user or the service personnel should NEVER perform during the UPS installation, operation or service work. PROHIBIT Safety Recommendations: If any problems are encountered while following this manual, contact the Toshiba Customer Support Center. G9000 MMS KIT Installation Manual 1000-2000kVA – 200150-001...
1.2 Qualified Personnel Only qualified persons are to install, operate or service this equipment according to all applicable codes and established safety practices. A qualified person must: Read this entire instruction manual carefully. Be skilled in the installation, construction or operation of the equipment and aware of the hazards involved. Be trained and authorized to safely energize, de-energize, clear, ground, lockout and tag circuits in accordance with established safety practices Be trained and authorized to perform the service, maintenance or repair of this equipment...
OVERVIEW TOSHIBA G9000 Uninterruptible Power Supply Systems (UPS) need an MMS KIT whenever two or more UPSs are installed in parallel operation configuration. Each UPS requires an MMS KIT installed to allow it to complete the communication circuit with other modules.
Part #1: Parallel Interface board (IFAU-16*) Part #2: Cable Part #3A, 3B: Cable Part #3C, 3D, 3E: Wire Part #4: Spacer Part #5: Ferrite Core Part #6: Dust Cover for LAN Jack Part #7: Screw(M3), Part #10:Screw(M4) Figure 3-1: MMS KIT Parts Identification G9000 MMS KIT Installation Manual 1000-2000kVA –...
Installation Procedures Unit: mm Step5A Ground bus Details (Upper right of bypass cabinet for 1000kVA UPS) Dust cover x12 Spacer x8 Step4 Step1 IFAU-16* Step2 Screw(M3) x8 Ferrite core Step3 Screw(M3) (Front cover) Details of A Step 1: Screw 8 spacers on the metallic plate (shown in red). Step 2: Secure the parallel interface board IFAU-16* on the spacers with M3 screws.
Details Unit: mm Step5A Ground bus (Upper right of bypass cabinet for 1330-2000kVA UPS) Dust cover x12 Spacer x8 Step4 Step1 Ferrite core Step2 Screw(M3) IFAU-16* Step3 Screw(M3) x8 Details of A Step 1: Screw 8 spacers on the metallic plate (shown in red). Step 2: Secure the parallel interface board IFAU-16* on the spacers with M3 screws.
DIA*/DIB* UPS#1 <-> UPS#2 .. UPS#(n) .. UPS#(N-1) <-> UPS#N TLA*/TLB CA*/CB* X - UPS#1 <-> UPS#2 .. UPS#(n) .. UPS#(N-1) <-> UPS#N - X Parallel control communication cables from/to other UPSs (See section 4 for details) Upper left of DIAOUT DIBOUT DIAIN DIBIN CAOUT CBOUT...
IMPORTANT NOTICE In cases where there are large amounts of slack LAN cables after installation: Keep cables away from the power conversion circuits and conductors in order to avoid interference in the parallel control communication. Do not roll cables as doing so may cause signal interference. PROHIBIT Example of 1000kVA Ground Bus...
Step 8: Setup the dip switch on IFAU-16* according to Table 4-1. Dip Switch(S1) Figure 4-5: Dip Switch Location on Parallel Interface Board (IFAU-16*) Table 4-1: Dip Switch Setting on Parallel Interface Board (IFAU-16*) No.1 No.2 No.3 No.4 No.5 No.6 System 1 and 2: ON 2 by MMS...
Step 9: Make sure the status of Jumpers on IFAU-16* according to Table 4-2. SHORT JP11 SHORT OPEN Figure 4-7: Location of Jumpers on Parallel Interface Board(IFAU-16*) Table 4-2: Status of Jumpers on Parallel Interface Board(IFAU-16*) Device Status SHORT SHORT JP11 OPEN G9000 MMS KIT Installation Manual 1000-2000kVA –...
When in Parallel Operation, the rectifier inputs to all G9000 UPS Systems in the Multi-Module System (MMS)-must be fed from a single source at all times including any operation of Automatic Transfer Switches. All G9000 bypass inputs must also be fed from a single source at all times (not necessarily the same source as the rectifier inputs). NOTE Parallel Operation System Connection Figure 5-1: Diagram of Power Wire Connections (Parallel Operation System)
Use Ethernet STP(Shielded Twisted Pair) Cable (Cat 6 or better) with RJ45 modular connectors for all communication cabling. Use of UTP (Unshielded Twisted Pair) Cable may cause malfunction. Total cable length from UPS-1 to UPS-n should be within 100m (330ft). NOTE *1: N(maximum) = 6 *2: Return from the last UPS...
Page 22