This chapter shows the codes for errors occurred in the dedicated function library and the corrective actions.
common
The following table shows the common error codes for the dedicated function library.
*1
Error code
Decimal
Hexadec
imal
1
0001H
2
0002H
66
0042H
67
0043H
69
0045H
70
0046H
77
004DH
102
0066H
103
0067H
130
0082H
131
0083H
16384 to
4000H to
20479
4FFFH
APPX
116
Appendix 1 Function error codes
Function error codes
Description
■Driver not started
The driver is not started.
■Timeout error
• A timeout occurred while waiting for the response.
• The module specified as the communication target is not
supported.
■Already opened error
The specified channel has already been opened.
■Already closed error
The specified channel has already been closed.
■Unsupported function performing error
An unsupported function in the target station was performed.
■Station number error
• The specified station number is incorrect.
• The request for other stations was issued to the own station,
or the network number was not '0' even though the station
number was the own station (FFH).
■Memory reservation error
■Resource shortage error
■Task over error
Securing sufficient memory failed. Or, there are too many tasks
using the dedicated function library.
■Data send error
■Restart error
Sending data failed, or an attempt was made to send data
during restart.
■Reception error
Receiving data failed.
■Device number error
• The specified device number is out of range.
• The specified bit device number is not a multiple of 8.
■Number of device points error
• The specified number of device points is out of range.
• The specified number of bit device points is not a multiple of 8.
■Errors detected in the access target CPU module
Corrective action
• Check the channel number.
• Correct the error that occurred when the driver is started.
• Check the status of the system drive of the MELIPC.
• Check if the operating system is running normally.
• Review the operating status and mounting condition of the
access target station.
• Retry on the user program.
• Increase the timeout value of MELSEC data link function.
• Check if the module specified as the communication target is
supported.
The open processing is required only one time.
(If this error occurred, the path of the correct channel will be
returned to the argument.)
The close processing is required only one time.
• Check the path of the channel, network number, and station
number.
• Check if the function performed in the target station is
supported.
Correct the network number and station number specified in the
user program.
• The memory may be insufficient. End other running tasks.
Alternatively, reduce the excess size.
• Reduce the number of tasks using the dedicated function
library and retry the operation.
• Review the size or number specified to the arguments of the
user program.
• Check if the MELIPC is running normally.
• Reset the MELIPC, or turn the power OFF and ON.
• Retry.
• Retry after completion of the restart.
• Check if the MELIPC is running normally.
• Reset the MELIPC.
• Retry.
• Check if the MELIPC is running normally.
• Reset the MELIPC, or turn the power OFF and ON.
Check the device number.
Check the specified number of device points.
Refer to the user's manual of the access target CPU module.