C Controller module dedicated function
The following table shows the error codes of the C Controller module dedicated functions.
Error code
Description
Decimal
Hexadec
imal
■Module identification error
-201
FF37H
The specified module identification is unavailable.
-203
FF35H
■I/O signal error
The specified I/O signal is out of range.
■I/O access size error
-204
FF34H
The specified access size of I/O signal is out of range.
-208
FF30H
■Offset error
• The specified offset is out of range.
• An AnS series module (buffer memory) was accessed.
■Memory size specification error
-209
FF2FH
• The specified offset and its size are out of range.
• The address of data storage buffer pointer is 0.
• The specified size is 0.
-210
FF2EH
■Read area size error
The read area size is smaller than the read size.
■Time setting error
-211
FF2DH
The specified time is out of range.
-217
FF27H
■Driver not started
The driver is not started.
■WDT type error
-220
FF24H
The specified WDT type is out of range.
-223
FF21H
■Memory reservation error
Reserving sufficient memory failed.
-224
FF20H
■LED setting value error
The specified LED setting value is out of range.
■Event number specification error
-225
FF1FH
The specified event number is out of range or duplicated.
-227
FF1DH
■Control code send error
Sending control code failed.
■Event timeout error
-231
FF19H
A timeout occurred while waiting for an event.
-232
FF18H
■CPU number specification error
The specified CPU number is incorrect.
■Event wait error
-234
FF16H
An error other than timeout occurred while the function waits
for the event.
-235
FF15H
■Number of event settings specification error
The specified number of event settings is out of range.
■Remote operation specification code error
-236
FF14H
The remote operation specification code is out of range.
-237
FF13H
■Detailed information character string specification error
The length of the specified character string was out of range
or characters which cannot be specified was specified.
■Event log registration error
-238
FF12H
Registering an event log failed.
-240
FF10H
■Clock data incorrect error
The clock data to be set or the read clock data is incorrect.
■Cycle specification error
-241
FF0FH
• The specified cycle is out of range.
• The cycle was set even when it had already been set.
-242
FF0EH
■Synchronization type specification error
The specified synchronization type is out of range.
Corrective action
Check the specified module identification.
Check the specified I/O signal.
Check the specified access size of I/O signal (I/O number and read/
write size in words).
Check the specified offset.
• Check the specified memory size.
• Check the offset and its size.
• Check the specified data storage buffer pointer.
• Check the read size.
• Check the read area size.
Check the specified time.
Check if the driver is started.
Check the specified WDT type.
Check if sufficient memory is available.
Check the specified LED setting value.
Check the specified event number.
• Retry.
• Check if the MELIPC is running normally.
• Reset the MELIPC.
• Increase the timeout time.
• Check if the interrupt event number (interrupt pointer number) is
set correctly.
Check the value of the specified CPU number.
• Check if a program is forcibly being terminated.
• Check if the MELIPC is running normally.
• Reset the MELIPC, or turn the power OFF and ON.
Check the number of specified event settings.
Check the specified remote operation specification code.
Correct the length of the specified character string or character
string data.
Reset the MELIPC, or turn the power OFF and ON.
• Check the clock data to be set.
• If this error occurs when reading the clock data, set the data
again.
• Check the specified cycle.
• Check if the cycle has been already set.
Check the specified synchronization type.
Appendix 1 Function error codes
A
APPX
119