Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Table of contents Table of contents Section 1 Introduction...............5 This manual..................5 Intended audience................6 Product documentation...............6 Product documentation set............6 Document revision history............. 7 Related documents................7 Document symbols and conventions..........10 Symbols..................10 Document conventions..............10 Section 2 Safety information............13 Symbols on the product..............13 Warnings..................
Page 8
Table of contents Wall mounting................27 Overview................27 Mounting procedure for wall mounting........27 How to reach the rear side of the IED........28 Side-by-side 19” rack mounting...........29 Overview................29 Mounting procedure for side-by-side rack mounting....29 IED in the 670 series mounted with a RHGS6 case....30 Side-by-side flush mounting............
Page 9
Table of contents Installing the serial communication cable for RS485......74 RS485 serial communication module.......... 74 Installing the serial communication cable for RS485 SPA/IEC..77 Data on RS485 serial communication module cable....79 Installing the GPS antenna...............79 Antenna installation..............79 Electrical installation..............81 Lightning protection..............
Section 1 1MRK514019-UEN A Introduction Section 1 Introduction This manual The installation manual contains instructions on how to install the IED. The manual provides procedures for mechanical and electrical installation. The chapters are organized in chronological order in which the IED should be installed. 670 series 2.0 IEC Installation manual...
Section 1 1MRK514019-UEN A Introduction Intended audience Product documentation 1.3.1 Product documentation set Engineering manual Installation manual Commissioning manual Operation manual Application manual Technical manual Communication protocol manual Cyber security deployment guideline IEC07000220-4-en.vsd IEC07000220 V4 EN Figure 1: The intended use of manuals in different lifecycles The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600.
Section 1 1MRK514019-UEN A Introduction assistance during the testing phase. The manual provides procedures for checking of external circuitry and energizing the IED, parameter setting and configuration as well as verifying settings by secondary injection. The manual describes the process of testing an IED in a substation which is not in service.
Page 14
Section 1 1MRK514019-UEN A Introduction Documents related to REC670 Identify number Application manual 1MRK 511 310-UEN Commissioning manual 1MRK 511 312-UEN Product guide 1MRK 511 313-BEN Technical manual 1MRK 511 311-UEN Type test certificate 1MRK 511 313-TEN Ordering form, REC670 Customized 1MRK 511 323-BEN Ordering form, REC670 Preconfigured 1MRK 511 324-BEN...
Page 15
Section 1 1MRK514019-UEN A Introduction Documents related to RET670 Identify number Application manual 1MRK 504 138-UEN Commissioning manual 1MRK 504 140-UEN Product guide 1MRK 504 141-BEN Technical manual 1MRK 504 139-UEN Type test certificate 1MRK 504 141-TEN Ordering form, RET670 Customized 1MRK 504 143-BEN Ordering form, RET670 Preconfigured 1MRK 504 144-BEN...
Section 1 1MRK514019-UEN A Introduction Document symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
Page 17
Section 1 1MRK514019-UEN A Introduction • Signals in frames with a shaded area on their right hand side represent setting parameter signals that are only settable via the PST or LHMI. • If an internal signal path cannot be drawn with a continuous line, the suffix -int is added to the signal name to indicate where the signal starts and continues.
Section 2 1MRK514019-UEN A Safety information Section 2 Safety information Symbols on the product All warnings must be observed. Read the entire manual before doing installation or any maintenance work on the product. All warnings must be observed. Class 1 Laser product. Take adequate measures to protect your eyes and do not view directly with optical instruments.
Page 20
Section 2 1MRK514019-UEN A Safety information Always use suitable isolated test pins when measuring signals in open circuitry. Potentially lethal voltages and currents are present. Never connect or disconnect a wire and/or a connector to or from a IED during normal operation. Hazardous voltages and currents are present that may be lethal.
Section 2 1MRK514019-UEN A Safety information Caution signs Whenever changes are made in the IED, measures should be taken to avoid inadvertent tripping. The IED contains components which are sensitive to electrostatic discharge. ESD precautions shall always be observed prior to touching components.
Section 2 1MRK514019-UEN A Safety information Note signs Observe the maximum allowed continuous current for the different current transformer inputs of the IED. See technical data. 670 series 2.0 IEC Installation manual...
Section 3 1MRK514019-UEN A Environmental aspects Section 3 Environmental aspects Sustainable development Sustainability has been taken into account from the beginning of the product design including the pro-environmental manufacturing process, long life time, operation reliability and disposing of the IED. Operational reliability and long life time have been assured with extensive testing during the design and manufacturing processes.
IEDs require careful handling before installation on site. • Check the IED to see if any damage occurred during transportation. If the IED has damaged during transportation, make a claim against the transport contractor, and notify the local ABB representative. 670 series 2.0 IEC Installation manual...
Returning an IED damaged in transit If damage has occurred during transport, appropriate actions must be taken against the latest carrier. Please inform the nearest ABB office or representative. Notify ABB immediately if there are any discrepancies in relation to the delivery documents.
Section 5 1MRK514019-UEN A Mounting Section 5 Mounting Required tools Generally, all the screws included in delivered mounting kits are of Torx type and a torque screwdriver of the same type is needed (Tx10, Tx15, Tx20 and Tx25). Use only the screws included in the mounting kit when mounting the plates and the angles on the IED.
Section 5 1MRK514019-UEN A Mounting Mounting the IED The IED can be rack, wall or flush mounted with the use of different mounting kits, see figure 2. An additional box of type RHGS can be mounted to one side of a 1/2 or 3/4 IED. The different mounting kits contain all parts needed including screws and assembly instructions.
Section 5 1MRK514019-UEN A Mounting IEC06000147-4-en.vsdx IEC06000147 V4 EN Figure 2: Different mounting methods Description A Flush mounting B 19” Panel rack mounting C Wall mounting D Side-by-side rack or flush mounting 5.3.1 Flush mounting 5.3.1.1 Overview The flush mounting kit can be used for case sizes: •...
Section 5 1MRK514019-UEN A Mounting To obtain IP54 class protection, an additional factory mounted sealing must be ordered when ordering the IED. 5.3.1.2 Mounting procedure for flush mounting IEC08000161-2-en.vsd IEC08000161 V2 EN Figure 3: Flush mounting details. PosNo Description Quantity Type Sealing strip, used to obtain IP54 class.
Section 5 1MRK514019-UEN A Mounting 5.3.2 19” panel rack mounting 5.3.2.1 Overview All IED sizes can be mounted in a standard 19” cubicle rack by using the for each size suited mounting kit which consists of two mounting angles, fastening screws and washers for the angles.
Section 5 1MRK514019-UEN A Mounting 5.3.2.2 Mounting procedure for 19” panel rack mounting IEC08000160-3-en.vsdx IEC08000160 V3 EN Figure 4: 19” panel rack mounting details The required torque for the screws is 3.5 Nm. Description Quantity Type Mounting angles, which can be mounted, either to the left or right side of the case.
Section 5 1MRK514019-UEN A Mounting 5.3.3 Wall mounting 5.3.3.1 Overview All case sizes, 1/2 x 19”, 3/4 x 19”,1/1 x 19”, can be wall mounted. It is also possible to mount the IED on a panel or in a cubicle. Use only the screws included in the mounting kit when mounting the plates and the angles on the IED.
Section 5 1MRK514019-UEN A Mounting PosNo Description Quantity Type Bushing Screw M4x10 Screw M6x12 or corresponding Mounting bar Screw M5x8 Side plate 5.3.3.3 How to reach the rear side of the IED The IED can be equipped with a rear protection cover recommended to be used with this type of mounting.
Section 5 1MRK514019-UEN A Mounting 5.3.4 Side-by-side 19” rack mounting 5.3.4.1 Overview IED case size 1/2 x 19” or 3/4 x 19” and RHGS cases can be mounted side-by-side up to a maximum size of 19”. For side-by-side rack mounting, the side-by-side mounting kit together with the 19”...
Section 5 1MRK514019-UEN A Mounting 5.3.4.3 IED in the 670 series mounted with a RHGS6 case An 1/2 x 19” or 3/4 x 19” size IED can be mounted with a RHGS (6 or 12 depending on IED size) case. The RHGS case can be used for mounting a test switch of type RTXP 24.
Section 5 1MRK514019-UEN A Mounting Use only the screws included in the mounting kit when mounting the plates and the angles on the IED. Screws with wrong dimension may damage the PCBs inside the IED. Please contact factory for special add on plates for mounting FT switches on the side (for 1/2 19"...
Section 5 1MRK514019-UEN A Mounting 5.3.6 Mounting the injection unit REX060 (REG670 only) The injection unit REX060 case size is 6U, 1/2 x 19”. REX060 can be rack, wall or flush mounted in the same way as the IED. For guidance, see instructions for rack mounting, wall mounting or flush mounting the IED in this manual.
Page 39
Section 5 1MRK514019-UEN A Mounting 217 [8,54] 155 [6,1] 2 [0,079] 84 [3,3] 84 [3,3] Ø 5,5 [0,22] IEC11000037-2-en.vsd IEC11000037 V2 EN Figure 11: Measure and drilling plan REX061 shall be mounted close to the generator in order to limit the exposure of the field circuit.
Section 5 1MRK514019-UEN A Mounting 5.3.7.2 Shunt resistor unit REX062 IEC11000038-1-en.vsd IEC11000038 V1 EN Figure 12: Shunt resistor unit REX062 217 [8,54] 155 [6,1] 2 [0,079] 84 [3,3] 84 [3,3] Ø 5,5 [0,22] IEC11000039-2-en.vsd IEC11000039 V2 EN Figure 13: REX062 measures and drilling plan REX062 shall be mounted close to the IED.
Page 41
Section 5 1MRK514019-UEN A Mounting be installed to get a open air convection and prevent contact with combustible material to the surface. 670 series 2.0 IEC Installation manual...
Section 6 1MRK514019-UEN A Connecting Section 6 Connecting Making the electrical connection 6.1.1 IED connectors 6.1.1.1 Overview The quantity and designation of connectors depend upon the type and size of the IED. The rear cover plates are prepared with space for the maximum of HW options for each case size and the cut-outs that are not in use are covered with a plate from factory.
Section 6 1MRK514019-UEN A Connecting Module Description Serial SPA/LON/IEC 60870-5-103 Used for SPA/LON/IEC 60870–5–103 communication modules (SLM) communication Optical ethernet module (OEM) PMC board for IEC 61850 based communication. mA input module (MIM) Analog input module with 6 independent, galvanically separated channels. GPS time synchronization module (GSM) Used to provide the IED with GPS time synchronization.
Section 6 1MRK514019-UEN A Connecting 6.1.1.3 Rear side connectors Table 4: Designations for 1/2 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X51 and X52 X301:A, B, C, D LDCM, IRIG-B or RS485 X302 LDCM or RS485...
Page 46
Section 6 1MRK514019-UEN A Connecting Table 5: Designations for 3/4 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X101 and X102 X301:A, B, C, D LDCM, IRIG-B or RS485 X302 LDCM or RS485 X303...
Page 47
Section 6 1MRK514019-UEN A Connecting Table 6: Designations for 3/4 x 19” casing with 2 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X71 and X301:A, B, C, D LDCM, IRIG-B or RS485 X302 LDCM or RS485 X303...
Page 48
Section 6 1MRK514019-UEN A Connecting Table 7: Designations for 1/1 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X161 and IOM or MIM X162 X301:A, B, C, D LDCM, IRIG-B or X302 RS485 LDCM or RS485...
Page 49
Section 6 1MRK514019-UEN A Connecting Table 8: Designations for 1/1 x 19” casing with 2 TRM slots Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X131 and IOM or MIM X132 X301:A, B, C, D LDCM, IRIG-B or X302 RS485 LDCM or RS485...
Page 51
Section 6 1MRK514019-UEN A Connecting mA input module (MIM) LOCATION=pN CONFIGURATION 1MRK002801-AC-15-670-1.2-PG V2 EN 1MRK002801-AC-11-670-1.2-PG V1 EN Figure 18: mA input Figure 17: Binary input module (BIM). module (MIM) Input contacts named XA corresponds to rear position X31, X41, and so on, and input contacts named XB to rear position X32, X42, and so on.
Page 52
Section 6 1MRK514019-UEN A Connecting Power supply module (PSM) INTERNAL FAIL Ready Fail Protective earth must be connected 1MRK002801-AC-7-670-1.2-PG V3 EN Figure 20: Power supply module (PSM) 1MRK002801-AC-12-670-1.2-PG V1 EN Figure 21: Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, and so on, and output contacts named XB to rear position X32, X42, and so on.
Page 53
Section 6 1MRK514019-UEN A Connecting 1MRK002801-AC-13-670-1.2-PG V1 EN Figure 22: Static output module (SOM) 1MRK002801-AC-14-670-1.2-PG V1 EN Figure 23: Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, and so on, and output contacts named XB to rear position X32, X42, and so on.
Section 6 1MRK514019-UEN A Connecting 6.1.1.4 Connection examples for high impedance differential protection WARNING! USE EXTREME CAUTION! Dangerously high voltages might be present on this equipment, especially on the plate with resistors. De-energize the primary object protected with this equipment before connecting or disconnecting wiring or performing any maintenance.
Page 55
Section 6 1MRK514019-UEN A Connecting Three-phase plate with setting resistors and metrosils. Protective earth is a separate 4 mm screw terminal on the plate. Necessary connection for three-phase metrosil set. Position of optional test switch for secondary injection into the high impedance differential IED. Necessary connection for setting resistors.
Section 6 1MRK514019-UEN A Connecting Description Scheme earthing point Ensure that only one earthing point exists in this scheme. One-phase plate with stabilizing resistor and metrosil. Protective earth is a separate 4 mm screw terminal on the plate. Necessary connection for the metrosil. Position of optional test switch for secondary injection into the high impedance differential IED.
Section 6 1MRK514019-UEN A Connecting en05000509.vsd IEC05000509 V1 EN Figure 26: Rear view of IED showing earthing points. Description Protective conductor terminal. For connection of the external protective (earth) conductor. Earth terminal. For internal protective bonding, do not use or remove. Earth terminal.
Section 6 1MRK514019-UEN A Connecting The auxiliary power wiring should have a minimum cross-sectional area of 1.0 mm and a voltage rating of 250 V. Branch circuit protection must be provided in the auxiliary power supply wiring to the IED, and if necessary it must be possible to disconnect manually from the power supply.
Page 59
Section 6 1MRK514019-UEN A Connecting proper electrical contact between the printed circuit board and the external wiring connected to the screw terminal block. If the IED is equipped with a test-switch of type RTXP 24, COMBIFLEX wires with 20 A sockets, 1.5mm² (AWG16) conductor area must be used to connect the auxiliary power.
Section 6 1MRK514019-UEN A Connecting IEC06000168 V3 EN Figure 29: Accessories PosNo Description Ferrule Bridge connector, used to jump terminal points in a connector. Table 10: Auxiliary power supply and binary I/O connectors Connector type Rated voltage Maximum conductor area Screw compression type 250 V AC 2.5 mm...
Page 61
Section 6 1MRK514019-UEN A Connecting IEC13000234-1-en.vsd GUID-682A59D0-950C-4D89-8318-984E0A8B2761 V1 EN Figure 30: Shield connection clamp The cable shield shall be properly connected to the IED chassis by the cable clamp with the maximum open conductor length of 40 mm between clamp and terminals. If double shielded cable is used, the inner cable shielding should be connected at the external equipment end only.
Section 6 1MRK514019-UEN A Connecting Making the electrical connection to the rotor and stator injection equipment (REG670 only) 6.2.1 Connectors for injection unit REX060, coupling capacitor unit REX061 and shunt resistor unit REX062 6.2.1.1 Injection unit REX060 1/2x19" (241.3 mm) Rear view Front view Module Slot...
Page 63
Section 6 1MRK514019-UEN A Connecting 1MRK002501-BA-4-PG V2 EN Figure 33: Stator injection module 670 series 2.0 IEC Installation manual...
Page 64
Section 6 1MRK514019-UEN A Connecting 1MRK002501-BA-5-PG V2 EN Figure 34: Rotor injection module 670 series 2.0 IEC Installation manual...
Section 6 1MRK514019-UEN A Connecting 6.2.1.3 Shunt resistor unit REX062 Bottom view Module Slot Terminal (217 mm) Front view REX062 (235 mm) 1MRK002556-BA-1-PG V2 EN Figure 37: Designation for shunt resistor unit casing Protective conductor terminal. For connection of the external protective (earth) conductor. 670 series 2.0 IEC Installation manual...
Section 6 1MRK514019-UEN A Connecting 1MRK002556-BA-2-PG V2 EN Figure 38: Shunt resistor module 6.2.2 Connecting injection unit REX060, coupling capacitor unit REX061 and shunt resistor unit REX062 The injection unit REX060 should be installed close to the IED in the same cubicle, or at minimum within 10 m distance of the IED.
Page 69
Section 6 1MRK514019-UEN A Connecting this type of equipment. The auxiliary power wiring should have a minimum cross- sectional area of 1.0 mm and a voltage rating of 250 V. Branch circuit protection must be provided in the auxiliary power supply wiring to the IED and, if necessary, it must be possible to disconnect it manually from the power supply.
Page 70
Section 6 1MRK514019-UEN A Connecting IEC11000225-2-en.vsd IEC11000225 V3 EN Figure 40: Stator connection example, with REX062 IEC11000236-2-en.vsd IEC11000236 V3 EN Figure 41: Stator connection example, without REX062 For connection details regarding REX060, REX061 and REX062, refer to section Connection diagrams in the REG670 Technical Manual. 670 series 2.0 IEC Installation manual...
Page 71
Section 6 1MRK514019-UEN A Connecting REX060 connections Table 11: Power X11 Signal Ready, Power off NO binary out Power off common binary out Fail, Power off NC binary out Power input positive Power input negative Table 12: Stator IED and sense connection X61 Signals Block injection, 220 V binary in Block injection, 110 V binary in...
Page 72
Section 6 1MRK514019-UEN A Connecting Table 14: Rotor injection and IED connection X81 Signal Block injection, 220 V binary in Block injection, 110 V binary in Block injection, 48 V binary in Block injection, Common binary in Injection Blocked NC binary out Voltage/Current Saturation NO binary out Common binary out Voltage A, analog out...
Page 73
Section 6 1MRK514019-UEN A Connecting REX061 Capacitor unit connections Table 16: Injection and rotor connection X1 Signal Rotor positive pole Positive pole Negative pole Rotor negative pole Rotor injection Injection earth. Internally connected to chassis and PE Table 17: Measurment connector X2 Signal Rotor + voltage divided by 1 000 Earth...
Section 6 1MRK514019-UEN A Connecting REX062 Shunt resistor unit connections Table 18: Injection via shunt resistors connection X1 Signal Injection Injection return Current sense output Current sense output Injection input, External shunt Injection input return, External shunt X1 connector. Connect each signal connector terminal of screw compression type with one 0.14 to 6 mm (AWG 35 - AWG 3) wire or with two 0.14 to 1.5 mm (AWG...
Page 75
Section 6 1MRK514019-UEN A Connecting REX060 VOLTAGE MEASURE (U) STATOR MODULE SIM CURRENT MEASURE (U) ROTOR MODULE RIM IEC11000210-1-en.vsd IEC11000210 V1 EN Figure 42: Connection to IED with two analogue voltage inputs Two different voltage inputs are used for stator and rotor voltage measurement and two other voltage inputs are used for stator and rotor current measurement.
Section 6 1MRK514019-UEN A Connecting If sufficient number of analog voltage inputs are available in the IED, alternative two with separate inputs for STTIPHIZ and ROTIPHIZ are recommended. Some settings are required for the analog voltage inputs. Set the voltage ratio for the inputs to 1/1, for example, VTSecx = 100 V VTPrimx = 0.1 kV The analog inputs are linked to a pre-processor block in the Signal Matrix Tool.
For location of X-21 LDCM , refer to section "Rear side connectors". The galvanic X.21 line data communication module uses a ABB specific PC*MIP Type II format. 670 series 2.0 IEC Installation manual...
Page 78
Section 6 1MRK514019-UEN A Connecting en07000196.vsd IEC07000196 V1 EN Figure 44: Overview of the X.21 LDCM module en07000239.wmf IEC07000239 V1 EN Figure 45: The X.21 LDCM module external connectors Earth selection connector for IO, screw terminals, 2-pole Earth pin Soft earth pin, see figure X.21 Micro D-sub 15 pole male connector according to the V11 (X:27) balanced version 670 series 2.0 IEC...
Page 79
Section 6 1MRK514019-UEN A Connecting 100k W 100nF Soft ground en07000242.vsd IEC07000242 V1 EN Figure 46: Schematic view of soft earth Earthing Three different kinds of earthing principles can be set (used for fault tracing): Direct earth - The normal earthing is direct earth, connect terminal 2 directly to the chassis.
Section 6 1MRK514019-UEN A Connecting Installing the serial communication cable for RS485 6.5.1 RS485 serial communication module Angle bracket Screw terminal RS485 Screw terminal Backplate en07000140.vsd IEC07000140 V1 EN Figure 47: The connection plate to the backplate with connectors and screws. This figure also shows the pin numbering from the component side Name 2-wire Name 4-wire...
Page 81
Section 6 1MRK514019-UEN A Connecting The distance between connection points should be < 1200 m (3000 ft), see Figures and 49. Only the outer shielding is connected to the IED with the cable clamp, shown in Figure 30. The cable shield shall be properly connected to the IED chassis with the cable clamp, where the maximum open conductor length is 40 mm (1.57”) between clamp and terminals, see Figure 30.
Page 82
Section 6 1MRK514019-UEN A Connecting External Equipment (PC) IEC13000230-1-en.vsd PE 1) 3) IEC07000142 V2 EN Figure 49: Communication cable installation, 4-wire Where: The inner shields shall be connected together (with an isolated terminal block) and only have one connection point in the whole system, preferably at the external equipment (PC). The outer shield shall be connected to the IED chassis in every cable end.
Section 6 1MRK514019-UEN A Connecting en03000110.vsd IEC03000110 V1 EN Figure 50: Cable contact, Phoenix: MSTB2.5/6-ST-5.08 1757051 Where: is cable is screw Pair separator Pair Shield Drain wire Conductor Overall shield Separator Jacket en07000139.vsd IEC07000139 V1 EN Figure 51: Cross section of communication cable The EIA standard RS-485 specifies the RS485 network.
Page 84
Section 6 1MRK514019-UEN A Connecting Normative references EIA Standard RS-485 - Electrical Characteristics of Generators and Receivers for Balanced Digital Multipoint Systems Transmission method RS-485 differential bipolar signaling Differential signal levels Two differential signal levels are defined: A+ =line A positive with respect to line B A- =line A negative with respect to line B Galvanic isolation The RS485 circuit shall be isolated from earth by:...
Section 6 1MRK514019-UEN A Connecting ExV is supplied by the Node at end of the Bus Segment The specifications of the components are: a) Ru + 5 V to Signal B = 390 W, 0.25 W ±2.5% b) Rt Signal B to Signal A = 220 W, 0.25 W ±2.5% c) Rd Signal A to GND...
Page 86
Section 6 1MRK514019-UEN A Connecting xx05000510.vsd IEC05000510 V1 EN PosNO Description GPS antenna TNC connector Console, 78x150 mm Mounting holes 5.5 mm Tab for securing of antenna cable Vertical mounting position (on antenna mast etc.) Horizontal mounting position Mount the antenna and console clear of flat surfaces such as buildings walls, roofs and windows to avoid signal reflections.
Section 6 1MRK514019-UEN A Connecting 99001046.vsd IEC99001046 V1 EN Figure 53: Antenna line-of-sight 6.6.2 Electrical installation Use a 50 ohm coaxial cable with a male TNC connector on the antenna end and a male SMA connector on the receiver end to connect the antenna to the IED. Choose cable type and length so that the total attenuation is max.
Section 7 1MRK514019-UEN A Checking installation Section 7 Checking installation Identifying hardware and software version The information of hardware and software versions of the IED are available on the label attached on the case of the IED. There are also module labels that can be used to identify the different modules inside the IED (such as input-output cards and so on).
Page 90
If the self supervision of the IED detects a diagnostic error during the start-up process, the green Ready LED flashes. Further information on the error may be visible on the local HMI under Main menu/Diagnostics/IED status/General. Note down the displayed information as reference when contacting ABB technical support. 670 series 2.0 IEC Installation manual...
Before removing the IED, make sure that auxiliary power is turned off and all wiring is disconnected. For upgrade purposes the IED does not need to be removed. Before removing the IED check with your local ABB office if the IED can be upgraded. 670 series 2.0 IEC...
1MRK514019-UEN A Removing, repairing and exchanging Sending the IED for repair In case of product problems, contact the nearest ABB office or representative for consultation and instructions. Exchanging the IED To exchange the IED with another identical unit, remove the IED and install the new one.
Section 9 1MRK514019-UEN A Technical data Section 9 Technical data Dimensions 9.1.1 Case without rear cover IEC08000164-2-en.vsd IEC08000164 V2 EN Figure 54: Case without rear cover 670 series 2.0 IEC Installation manual...
Page 94
Section 9 1MRK514019-UEN A Technical data xx08000166.vsd IEC08000166 V1 EN Figure 55: Case without rear cover with 19” rack mounting kit Case size (mm) A 6U, 1/2 x 19” 265.9 223.7 201.1 252.9 205.7 190.5 203.7 465.1 187.6 482.6 6U, 3/4 x 19” 265.9 336.0 201.1...
Section 9 1MRK514019-UEN A Technical data 9.1.2 Case with rear cover IEC08000163-2-en.vsd IEC08000163 V2 EN Figure 56: Case with rear cover 670 series 2.0 IEC Installation manual...
Page 96
Section 9 1MRK514019-UEN A Technical data xx08000165.vsd IEC08000165 V1 EN Figure 57: Case with rear cover and 19” rack mounting kit IEC05000503-2-en.vsd IEC05000503 V2 EN Figure 58: Rear cover case with details Case size (mm) A 6U, 1/2 x 19” 265.9 223.7 242.1...
Section 9 1MRK514019-UEN A Technical data 9.1.4 Side-by-side flush mounting dimensions IEC06000182-2-en.vsd IEC06000182 V2 EN Figure 60: A 1/2 x 19” size IED side-by-side with RHGS6 xx05000505.vsd IEC05000505 V1 EN Figure 61: Panel-cut out dimensions for side-by-side flush mounting Case size (mm) Tolerance ±1 ±1...
Section 10 1MRK514019-UEN A Glossary Section 10 Glossary Alternating current Actual channel Application configuration tool within PCM600 A/D converter Analog-to-digital converter ADBS Amplitude deadband supervision Analog digital conversion module, with time synchronization Analog input ANSI American National Standards Institute Autoreclosing ASCT Auxiliary summation current transformer Adaptive signal detection...
Page 102
Section 10 1MRK514019-UEN A Glossary CCITT Consultative Committee for International Telegraph and Telephony. A United Nations-sponsored standards body within the International Telecommunications Union. CAN carrier module CCVT Capacitive Coupled Voltage Transformer Class C Protection Current Transformer class as per IEEE/ ANSI CMPPS Combined megapulses per second Communication Management tool in PCM600...
Page 103
Section 10 1MRK514019-UEN A Glossary DHCP Dynamic Host Configuration Protocol DIP-switch Small switch mounted on a printed circuit board Digital input DLLB Dead line live bus Distributed Network Protocol as per IEEE Std 1815-2012 Disturbance recorder DRAM Dynamic random access memory Disturbance report handler Digital signal processor Direct transfer trip scheme...
Page 104
Section 10 1MRK514019-UEN A Glossary Gas-insulated switchgear GOOSE Generic object-oriented substation event Global positioning system GSAL Generic security application Generic substation event HDLC protocol High-level data link control, protocol based on the HDLC standard HFBR connector type Plastic fiber connector Human-machine interface HSAR High speed autoreclosing...
Page 105
Section 10 1MRK514019-UEN A Glossary function. One instance of a function is identical to another of the same kind but has a different number in the IED user interfaces. The word "instance" is sometimes defined as an item of information that is representative of a type. In the same way an instance of a function in the IED is representative of a type of function.
Page 106
Section 10 1MRK514019-UEN A Glossary Overcurrent protection Optical Ethernet module OLTC On-load tap changer OTEV Disturbance data recording initiated by other event than start/pick-up Overvoltage Overreach A term used to describe how the relay behaves during a fault condition. For example, a distance relay is overreaching when the impedance presented to it is smaller than the apparent impedance to the fault applied to the balance point, that is, the set reach.
Page 107
Section 10 1MRK514019-UEN A Glossary Short circuit location Station control system SCADA Supervision, control and data acquisition System configuration tool according to standard IEC 61850 Service data unit Serial communication module. SMA connector Subminiature version A, A threaded connector with constant impedance.
Page 108
Section 10 1MRK514019-UEN A Glossary TNC connector Threaded Neill-Concelman, a threaded constant impedance version of a BNC connector Trip (recorded fault) TPZ, TPY, TPX, TPS Current transformer class according to IEC Transformer Module. This module transforms currents and voltages taken from the process into levels suitable for further signal processing.
Page 110
Contact us Note: For more information please contact: We reserve the right to make technical changes or modify the contents of this document without prior notice. ABB AB ABB AB does not accept any responsibility whatsoever for potential Substation Automation Products errors or possible lack of information in this document.