GE AV-300i User Manual page 61

Hide thumbs Also See for AV-300i:
Table of Contents

Advertisement

Description:
I/O CONFIG
Commands
Commands src
I/O CONFIG
In the Block configurations it is possible to set the following parameters:
- Command select
Terminal level
Terminal edge
Digital level
Digital edge
I/O keys
- En/Disable mode
- Spd 0 dis dly
Description:
I/O CONFIG
Commands
Commands cfg
The monitor menu displays:
Enable cmd mon
Start cmd mon
FastStop cmd mon
AV-300i Version 2 User's Guide
Term StrStp src
Term Start src
Term Stop
src
Dig Enable src
Dig StrStp src
FastStop src
SAVE PARAMETERS
Logic for the Start/Stop Edge or Level sensitive signal
The drive is controlled via terminal strip using the level sensitive mode
The drive is controlled via terminal strip using the edge sensitive mode
The drive is controlled from a communication or application card using
the level sensitive mode
The drive is controlled from a communication or application card using
the edge sensitive mode
The drive is controlled from the keyboard using the I O keys
Action time to the stop condition. Setting of this parameter is not allowed
while terminal enable is active. The drive can act:
·
With the enable and start/stop commands controlled independently
by the operator ( En/Disable mode = Off )
·
With just the start/stop command, while the enable and disable com-
mand is controlled by the drive. In this case with the start command the
drive enables itself. When the stop command is generated (and/or fast
stop according to the En/Disable mode selection), the Drive reaches a
zero speed and after a Spd 0 dis dly time, it disables itself automati-
cally (for more details see section 1.5.2.1.).
Delay time between the zero speed and the disabling procedure
Command select
En/Disable mode
Spd 0 dis dly
it displays the Enable command state
it displays the Start command state
it displays the Fast Stop command state
—————— Function Description ——————
Ch.1
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents