Overcurrent release for ac circuit-breaker
Hide thumbs Also See for 3WN6:
Table of Contents

Advertisement

misc. symU (only possible with measurement module and voltage
transformer): here is set the operating value for the permissible
voltage unbalance of the phases for the extended protective functions.
The adjustable values are in the range of 5 to 50 % or "off". If the
menu option relay opt is enabled, on occurrence of the parameterized
unbalance, the output "optional signal" is set and the circuit-breaker
is tripped after elapse of the delay time set under relay tx.
misc. EF (only possible with measurement module and voltage
transformer): here is set the operating value for the permissible
reversed energy flow direction for the extended protective functions.
The adjustable values are in the range of -2000 kW to 2000 kW or
"off". If the menu option relay opt is enabled, on occurrence of the
parameterized unbalance, the output "optional signal" is set and the
circuit-breaker is tripped after elapse of the delay time set under
relay tx.
misc. f< (only possible with measurement module and voltage
transformer): here is set the operating value for underfrequency for
the extended protective functions. The adjustable values are in the
range of 15 Hz to 500 Hz or "off". If the menu option relay opt is
enabled, on occurrence of the parameterized unbalance, the output
"optional signal" is set and the circuit-breaker is tripped after elapse
of the delay time set under relay tx.
misc. f> (only possible with measurement module and voltage
transformer): here is set the operating value for overfrequency for
the extended protective functions. The adjustable values are in the
range of 15 Hz to 500 Hz or "off". If the menu option relay opt is
enabled, on occurrence of the parameterized unbalance, the output
"optional signal" is set and the circuit-breaker is tripped after elapse
of the delay time set under relay tx.
misc. U< (only possible with measurement module and voltage
transformer): here is set the operating value for undervoltage for the
extended protective functions. The adjustable values are in the
range of off, 100 V to 1000 V or "off". If the menu option relay opt is
enabled, on occurrence of the parameterized unbalance, the output
"optional signal" is set and the circuit-breaker is tripped after elapse
of the delay time set under relay tx.
misc. U> (only possible with measurement module and voltage
transformer): here is set the operating value for overvoltage for the
extended protective functions. The adjustable values are in the
range of 100 V to 1250 V or "off". If the menu option relay opt is
enabled, on occurrence of the parameterized unbalance, the output
"optional signal" is set and the circuit-breaker is tripped after elapse
of the delay time set under relay tx.
misc. I _off: here is set the operating value for load shedding. The
adjustable values are in the range of (50 % to 150 %) x l r or "off".
(only possible with additional functions 2)
Caution
The signal is only active after elapse of the delay time
set under menu option Relay tx.
Note:
If the signal "advance a_trip" is to be used, this
parameter must be set to off.
misc. I _on: here is set the operate value for load restoring. The
adjustable values are in the range of (50 % to 150 %) x I r or "off".
(only possible with additional functions 2)
Caution
The signal is only active after elapse of the delay time
set under menu option Relay tx.
18
value f
value P
protec.
misc.
status
status
In
Test
status In
status Test
= 1600 A
=System OK
Measure values are examples
Menu status
In this menu option, status information is displayed.
status D No.:
encoded circuit-breaker ID number (Part 1)
status L No.:
encoded circuit-breaker ID number (Part 2)
The manufacturing and testing data of the respec-
tive release is stored at Siemens under these iden-
tifikation numbers. This enables quick clarification
in the event of any queries regarding the electronic
release.
status bus:
higher-level communication bus system (if present)
status l n :
circuit-breaker rated current
status Test:
result of the internal release test
value P
protec.
misc.
status
relay
relay
relay
tx
relay tx
relay g
= 10 s
= on/off
relay tx
relay g
# 15 s
# on/off
relay tx
relay g
? 15 s
? on/off
relay tx
relay g
= 15 s
= on/off
Parameterizing values are examples
Menu relay
relay g:
on - exceeding the operate value of the earth-fault protection leads
to trip
off - exceeding the operate value of the earth-fault protection
activates the earth-fault LED. Indication can only be reset by
pressing the CLEAR button after the operate value has been
undershot
This is possible only on overcurrent releases E/F, J/K and P.
relay temp:
on - exceeding the temperature limit in the release enclosure
activates the optional signal and the temperature LED (the
optional signal must be enabled by the relay opt. menu option)
off - exceeding the temperature limit in the release enclosure
activates the temperature LED
relay opt.
on - the optional signal is activated if at least one of the enabled
causes is present (I.E. misc. syml or relay temp) and the
circuit-breaker is tripped after elapse of the delay time set
under relay tx.
off - optional signal and optional tripping are disabled
relay tx:
Delay time for menu options:
misc. syml, misc. symU, misc. EF, misc. f<, misc. f>, misc. U<,
misc. U>, misc. I _off, misc. I _on.
value U
value I
menu
relay
status
status
status
status
D-Nr.
L-Nr.
Bus
status D-Nr
status L-Nr
status Bus
= 23456
= 3
= RS485
value f
value U
value I
Menu
relay
relay
g
temp
opt.
relay temp
relay opt.
= on/off
= on/off
relay temp
relay opt.
#= on/off
# on/off
relay temp
relay opt.
? on/off
? on/off
relay temp
relay opt.
= on/off
= on/off

Advertisement

Table of Contents
loading

This manual is also suitable for:

3wx3641-.jn.03wx3641-.jp.0

Table of Contents