SUN2000-(8KTL-20KTL)-M2
User Manual
Table 8-2 Common alarms and troubleshooting measures
Alarm
Alarm Name
ID
2001
High String
Input Voltage
2002
DC Arc Fault
2011
String Reverse
Connection
Issue 01 (2020-07-02)
Warning: The inverter works properly. The output power decreases or some
authorization functions fail due to external factors.
Alarm
Possible Cause
Severity
Major
The PV array is not
properly
configured.
Excessive PV
modules are
connected in series
to the PV string,
and therefore the
open-circuit voltage
exceeds the
maximum inverter
operating voltage.
Cause ID 1 = PV1
and PV2
Cause ID 2 = PV3
and PV4
Major
The PV string
power cable arcs or
is in poor contact.
Cause ID 1 = PV1
and PV2
Cause ID 2 = PV3
and PV4
Major
The PV string
polarity is reversed.
Cause ID 1 = PV1
Cause ID 2 = PV2
Cause ID 3 = PV3
Cause ID 4 = PV4
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting Suggestion
Reduce the number of PV modules
connected in series to the PV string
until the PV string open-circuit
voltage is less than or equal to the
maximum inverter operating
voltage. After the PV array is
correctly configured, the inverter
alarm disappears.
Check that the PV string power
cable does not arc and is in good
contact.
Check whether the PV string is
reversely connected to the
SUN2000. If yes, wait until the PV
string current decreases below 0.5
A, set DC SWITCH to OFF, and
adjust the PV string polarity.