Connecting the Power Cable and Signal Cable for the Water Cooling Module
Water cooling module
power cables supply
on the Indoor unit
Water cooling
module
9.3
Connecting T/H Sensors Outside Cabinets
1. Connect the T/H sensor cables.
The T/H sensors in the aisles should be
installed on the door frame of IT cabinets,
and1.5 m (33U) away from the ground. After
the sensor is secured, set the sensor
address according to the following table.
2. Set the DIP switches on the T/H sensors.
Power cable hole
17
Signal cable hole
Signal cables for the indoor units
Water cooling
module