1. First startup flowchart
Start
Tap Start on the home screen.
After tapping Yes, the barcode and the
verification code are shown on the screen.
Open the Service Expert app.
Tap StartUp > Offline Activation on APP
Enter Bar code and Verification code,
and tap Generate PWD.
Enter the generated startup password on
the screen of smart cooling product.
Tap Enter. The screen turns to Wizard
Startup.
No
Refrigerant is
fully charged?
Tap No on Wizard Startup screen to exit
wizard startup.
Tap Start on the home screen and choose
Maint > Diagnostic Mode > Enter.
Set the compressor to 3000 rpm.
Charge the remaining amount of refrigerant
from low-pressure needle valve.
Choose Maint > Diagnostic Mode > Exit
and tap Shutdown on the home screen.
Choose Maint > Wizard Startup to enter
wizard startup.
Go to step 2
2. Wizard startup flowchart
Commissioning
commissioning
Success
commissioning
Success
commissioning
commissioning
Yes
commissioning
Cooling system
commissioning
Tap Yes
on Wizard
Startup
screen to
enter
wizard
startup.
25
Start
No
Precautions
Yes
Select
Fail
items
Fail
Indoor fan
Fail
Electric heater
Fail
Humidifier
Condensate
Fail
pump
Outdoor fan
End
If a water cooling module
is installed outdoors,
outdoor fan
commissioning is not
implemented.
Commissioning
interrupted
(Handle the
fault by
referring to the
tips displayed
on the home
screen.
Perform wizard
startup after
the handling.)

Advertisement