Hydran* 201i Instruction Manual
6. Depending on the selected communication protocol, start the Hydran Host or
Perception software on the PC.
Perception User Manual for more information.
7. In the Network Settings menu of the Hydran Host software, set the network
configuration to the Gas Monitor ID numbers that were assigned to each H201Ti
in the step 5 above.
8. In the Setup menu of the Hydran Host software, check the communication by
accessing the H201Ti(s). The Communications Status indicator (yellow, DS6; item
23 in Figure 4-3) flickers when the PC communicates with the H201Ti(s).
9. In the Network Survey window of the Hydran Host software, verify the PC is
communicating with each H201Ti (there are no Does not answer warnings in the
Status text boxes).
10. If the communication cannot be established:
• Ensure the H201Ti identification numbers entered in the Hydran Host software
correspond to those entered in each H201Ti (Gas Monitor ID parameters).
• Verify the wiring of all supervisory link cables.
• Verify the wiring of the RS-485 local network link.
• Finally, disconnect the RS-485 link cable from all H201Cis and reinstall the
local network, one H201Ci at a time.
11. In the Relays/Analog window of the Hydran Host software, change the Relay
Mode of each relay from Force OFF to Force ON and back; this should change the
state of the alarm relays from On to Off, thus confirming good communications
through the supervisory links. Following each step:
• Verify the state of the H, HH and OK LED's on each H201Ti.
• Ensure the Communications Status indicator (yellow, DS6; item 23 in Figure 4-
3) flickers inside each H201Ci-C when the host computer communicates with
any H201Ti of the H201Ci-C.
12. When the test is completed, in the Relays/Analog window of the Hydran Host
software, restore the Relay Mode of each relay to Normal.
13. Disconnect all communication cables (supervisory links, RS-485 LAN and RS-232
or USB to the PC).
14. Restore the original communication settings in each H201Ti as noted in the step 4
above.

8.2.4 Completing the Verification

This completes the incoming verification of the Hydran 201Ci-C.
1. Disconnect all the H201Tis from the power outlets.
2. Disconnect all the H201Ci-Cs from the power outlets.
3. Remove all supply cables.
4. Remove all communication cables.
5. Store the H201Tis and the H201Ci-Cs in their respective boxes, ready for
installation.
6. If the H201Tis are not installed immediately, refer to Section 7.1.4.
7. If the H201Ci-Cs are not installed immediately, refer to Section 8.1.3.
MA-033
Rev. 14.0, 12-Nov-18