BaudRate to the same speed as the one indicated in the Power Stations Set-Up
window for this power station.
8. If the H201Ti communication speed is set for the first time, you must initialize the
H201Ci's modem with this communication speed. To do so, access the submenu
Communication of one of the H201Ti's connected to this H201Ci, select the Force
HostCall command and press ENTER.
Note: This task can be performed even if the H201Ci's modem is not connected to a
telephone line and even if this modem is not yet programmed with a telephone number.
9. If the H201Ti's Call OnAlarm command is not used (the H201Ci's modem is not
programmed with the telephone number of the host computer's modem), you
must use the Hydran Host software to trigger the communications between the
two modems. In the Hydran Host software, start the Hydran Host module; click
Remote and then Call Now (see the Hydran Host Software Manual).
10.
Verify the status of communications with the H201Ti's in the Network Survey
window of the Hydran Host software (see the Hydran Host Software Manual).
Note: The Hydran Host software, the communication software and the modem must use
the same communication port (COM1 or COM2).

10.6.3 Configuring the Call OnAlarm Mode

Prior to use the Call OnAlarm mode, make sure of the following:
• The installation of the Hydran 201i System is completed.
• Hydran protocol is used
• The network configuration is defined in the Hydran Host software (see the Hydran
Host Software Manual).
• The Hydran 201Ci Controller's modem is programmed with the telephone number
of the host computer's modem.
To use the Call OnAlarm mode, proceed as follows:
1. In the Hydran Host software, start the Hydran Host module.
2. Click Remote.
3. In the Remote Access window, select the desired power station.
4. Click Put on Watch.
The following actions are then performed:
1. The Hydran Host software initializes the host computer's modem.
2. This modem telephones to the H201Ci's modem.
3. The Hydran Host software sets to Call OnAlarm the CommMode parameter of all
Hydran 201Ti's in the Hydran 201i System or in the local network.
4. The Hydran Host software hangs up.