• In the H201Ti: To the Supervisory Link and Analog Output Termination Board
(item 9 in Figure 3-4).
• In the H201Ci-C: To the terminals 21 to 24 of the Main Terminal Block (item 5
in Figure 4-2).
• In the H201Ci-1: To the terminals 21 to 24 of the Main Terminal Block (item 6
in Figure 4-6).

10.1.1 TDM Pulse

The TDM pulse is used only with the Hydran 201Ci-1 Controller to transfer two pieces of
information from the Hydran 201Ti to the H201Ci-1 itself:
• Actual dissolved gas level: This analog signal varies from 0 to 100% (0 to
2,000ppm) with a resolution of 1 part in 4,000.
• Alarm relays status: This digital information has four possible values, namely
Normal, High, High-High and Fail.
The relationship between the alarm relay states and the status of the H201Ti, of the TDM
signal and of the H201Ci-1 is shown in Table 10-1 below.
Alarm
Hydran 201Ti
AC
power
Fail
None
OK
H
OK
H-H
OK
Fail
OK
-
-
-
-
-
Out
a.
- = without consequence; H = High Alarm; HH = High-High Alarm; Sup = Supervisory.
b.
On = Normal (no alarm); Off = Alarm
Table 10-1: Alarm Relay States and Status of the H201Ti, TDM Signal and H201Ci-1
Page 144
Sup
a
Link
Relays
H
HH
b
On
Off
Off
OK
On
On
Off
OK
On
-
On
OK
Off
-
-
OK
-
-
-
Broken
-
-
-
-
Off
Off
Off
-
Hydran* 201i Instruction Manual
TDM
a
Signal
a
AC
power
Normal
OK
H
OK
H-H
OK
Fail
OK
Fail
OK
-
Out
-
-
Hydran 201Ci-1
a
Relays
ppm
Display
Fail
H
HH
b
On
Off
Off
On
On
On
Off
On
On
On
On
On
OK
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
MA-033
Rev. 14.0, 12-Nov-18