ABB ACS880 Electrical Planning Instructions page 14

Single drive cabinets and modules
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

14 Electrical planning guidelines
This table shows the requirements when an ABB motor is in use.
Motor
Nominal AC supply
type
voltage
Random-
U
≤ 500 V
N
wound
500 V < U
≤ 600 V
N
M2_, M3_
and M4_
600 V < U
≤ 690 V
N
(cable length ≤
150 m)
600 V < U
≤ 690 V
N
(cable length >
150 m)
Form-
380 V < U
≤ 690 V
N
wound
HX_ and
AM_
1)
380 V < U
≤ 690 V
Old
N
form-
wound
HX_ and
modular
0 V < U
≤ 500 V
Random-
N
wound
500 V < U
≤ 690 V
N
HX_ and
2)
AM_
HDP
Consult the motor manufacturer.
1) manufactured before 1.1.1998
2) For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.
Motor insula-
ABB du/dt and common mode filters, insulated N-end
tion system
P
< 100 kW
N
and frame
size <
IEC 315
P
< 134 hp
N
and frame
size <
NEMA 500
Standard
-
Standard
+ du/dt
or
Reinforced
-
Reinforced
+ du/dt
Reinforced
-
Standard
n.a.
Check with the
+ N + du/dt with voltages over 500 V + CMF
motor manu-
facturer.
Enamelled
wire with fiber
glass taping
Requirement for
motor bearings
100 kW ≤ P
< 350
N
kW
or
IEC 315 ≤ frame size
< IEC 400
134 hp ≤ P
< 469 hp
N
or
NEMA 500 ≤ frame
size ≤ NEMA 580
+ N
+ N + du/dt
+ N
+ N + du/dt
+ N
+ N + CMF
+ N + CMF
+ N + du/dt + CMF
P
≥ 350 kW
N
or
frame size ≥ IEC 400
P
≥ 469 hp
N
or
frame size >
NEMA 580
+ N + CMF
+ N + du/dt + CMF
+ N + CMF
+ N + du/dt + CMF
+ N + CMF
P
< 500 kW:
N
+N + CMF
P
≥ 500 kW:
N
+N + du/dt + CMF

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs580Ach580Acq580Ah580-07Acq580-07

Table of Contents