Download Print this page

Siemens SIMATIC S7-200 Series Manual page 12

Ethernet gateway for simatic mpi/ profibus driver
Hide thumbs Also See for SIMATIC S7-200 Series:

Advertisement

4.2
Setup Items in Offline Mode
• Refer to the Maintenance/Troubleshooting manual for information on how to enter offline
Cf.
 Communication Settings
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Equipment Settings] in off-line mode.
Touch the External Device you want to set from the list that appears.
(Page 1/2)
Setup Items
Port No.
Timeout
Retry
Wait To Send
GP-Pro EX Device/PLC Connection Manual
mode or about the operation.
Maintenance/Troubleshooting Manual "Offline Mode"
Enter a port number of the Display, using 1024 to 65535. Check into [Auto], and a port
number is set automatically.
Use an integer from 1 to 127 to enter the time (s) for which Display waits for the response
from External Device.
In case of no response from the External Device, use an integer from 0 to 255 to enter how
many times the Display retransmits the command.
Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving
packets to transmitting next commands.
Ethernet Gateway for SIMATIC MPI/PROFIBUS Driver
Setup Description
12

Hide quick links:

Advertisement

loading