Parameter Description

3.25 LC-## Logic Controller

3.25.1 LC-## Logic Controller
Logic Controller (LC) is a sequence of user-defined actions
(see parameter LC-52 Logic Controller Action [x]) executed by
the LC when the associated user-defined event (see
parameter LC-51 Logic Controller Event [x]) is evaluated as
TRUE by the LC. Events and actions are each numbered
and linked together in pairs. This means that when [0]
event is fulfilled (attains the value TRUE), [0] action is
executed. After this, the conditions of [1] event are
evaluated and if evaluated TRUE, [1] action is executed and
so on. Only 1 event is evaluated at any time. If an event is
evaluated as FALSE, nothing happens (in the LC) during the
current scan interval and no other events are evaluated.
This means that when the LC starts, it evaluates [0] event
(and only [0] event) at each scan interval. Only when [0]
event is evaluated TRUE, the LC executes [0] action and
starts evaluating [1] event. It is possible to program from 1
to 20 events and actions.
When the last event/action has been executed, the
sequence starts over again from [0] event/[0] action.
Illustration 3.74 shows an example with 3 events/actions
Illustration 3.74 Example with 3 Events/Actions
Starting and stopping the LC
Start and stop the LC by selecting [1] On or [0] Off in
parameter LC-00 Logic Controller Mode. The LC always starts
in state 0 (where it evaluates [0] event). The LC starts when
the start event (defined in parameter LC-01 Start Event) is
evaluated as TRUE (provided that [1] On is selected in
parameter LC-00 Logic Controller Mode). The LC stops when
the stop event (parameter LC-02 Stop Event) is TRUE.
Parameter LC-03 Reset Logic Controller resets all LC
parameters and starts programming from scratch.
3.25.2 LC-0# LC Settings
Use the LC settings to activate, deactivate, and reset the
Logic Controller.
DET-620D
AF-600 FP™ Programming Guide
LC-00 Logic Controller Mode
Option:
[0]
*
[1]
LC-01 Start Event
Option:
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[10]
Out of speed
range
[11]
Below speed low See parameter group E-2# for further
[12]
Above speed
high
[13]
Out of feedb.
range
[14]
Below feedb. low
[15]
Above feedb.
high
[16]
Thermal warning See parameter group E-2# for further
[17]
Line voltage out
of range
[18]
Reversing
[19]
Warning
03/2016 All rights reserved.
Function:
Off
Disables the logic controller.
On
Enables the logic controller.
Function:
Select the boolean (TRUE or FALSE)
input to activate Logic Controller.
Enters the fixed value of FALSE in the
logic rule.
Enters the fixed value TRUE in the logic
rule.
See parameter group E-2# for further
description.
See parameter group E-2# for further
description.
See parameter group E-2# for further
description.
See parameter group E-2# for further
description.
See parameter group E-2# for further
description.
See parameter group E-2# for further
description.
See parameter group E-2# for further
description.
See parameter group E-2# for further
description.
description.
See parameter group E-2# for further
description.
description.
See parameter group E-2# for further
description.
See parameter group E-2# for further
description.
See parameter group E-2# for further
description.
3
3
183