Recommended Cross-Sectional
Areas for Power Cables
Input I current (A)
Recommended circuit
Breaker
Input I
Recommended
cross-sectional
2
area (mm
)
Input II current (A)
Recommended circuit
Breaker
Input II
Recommended
cross-sectional
2
area (mm
)
Maximum discharge
current (A)
Battery
Recommended
cable
cross-sectional
2
area (mm
)
Recommended Cross-Sectional Areas for Output Cables
Air conditioner (40 A)
Recommended cross-sectional
2
area (mm
)
Air conditioner (63 A)
Recommended cross-sectional
2
area (mm
)
Lighting system
Recommended cross-sectional
2
area (mm
)
IT load (40 A)
Recommended cross-sectional
2
area (mm
)
IT load (63 A)
Recommended cross-sectional
2
area (mm
)
UPS5000-E-
125K (ATS)
385
Three-pole,
400 A
L1
L2
4 x 185
L3
N
PE
95
385
Three-pole,
400 A
L1
L2
4 x 185
L3
N
PE
95
411
+
2 x 95
N
2 x 95
-
2 x 95
PE
95
L1
L2
L3
N
PE
L1
L2
L3
N
PE
L
N
PE
L
N
PE
L
N
PE
6
UPS5000-E-
UPS5000-E-
125K (MCCB)
50K (ATS)
385
184
Three-pole,
Three-pole,
400 A
250 A
4 x 185
4 x 95
95
50
N/A
184
Three-pole,
N/A
250 A
N/A
4 x 95
N/A
50
411
164
2 x 95
95
2 x 95
95
2 x 95
95
95
50
Cable Specifications
5 x 6
5 x 10
3 x 2.5
3 x 6
3 x 10
UPS5000-E-
50K (MCCB)
184
Three-pole,
250 A
4 x 95
50
N/A
N/A
N/A
N/A
164
95
95
95
50

Advertisement