Setting The Profibus Address At The G120 Dp; Loading The Software - Siemens SINAMICS G110M Manual

Speed control of a startdrive with tia portal via profibus dp with safety integrated (via terminal) and hmi
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

3 Setting up and commissioning the application

3.4 Setting the PROFIBUS address at the G120 DP

3.4
Setting the PROFIBUS address at the G120 DP
For this application example, use the DIP switch at the SINAMICS G120 to adjust
the bus address 3.
Figure 3-2: Setting the PROFIBUS address at the SINAMICS G120 DP
For the settings to become effective, perform a "POWER ON"
(switch off the voltage of the SINAMICS drive until all LEDs are dark).
3.5

Loading the software

NOTICE
Should you use a different SINAMICS converter or motor than specified in
, you need to perform your own configuration. In this case, follow the
2-1
instructions in chapter
this may cause damage.
This chapter describes how, in TIA Portal V13, you...
...load the STEP 7 program into the SIMATIC S7-1200,
...load the drive configuration into the SINAMICS G120, and
...load the control panel configuration into the HMI KTP600.
A requirement is that the software has been installed on your PG/PC according
to
Table 2-2
The procedure described in the step table below represents one
Note
configuration option of connecting a SINAMICS G120 to a SIMATIC S7-1200
via PROFIBUS, and operate it. TIA Portal offers several possible solutions
that differ to a greater or lesser degree from the procedure shown here.
The download to SINAMICS G120 is performed via USB.
SINAMICS G120 DP at S7-1200
Entry-ID: 70155469,
V1.4,
before loading the software into the device. Otherwise,
6
.
07/2018
Table
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents