NOTE
Ferrule terminal commercially available (as of December 2019. The product may be changed without notice.)
Terminal
Wire size (mm
screw size
0.3
M2
0.5
2.
Loosen the terminal screw and insert the cable into the terminal.
Tighten each cable with fixing screws to the recommended tightening torque.
<Cable connection example>
Screw size
M2
0.22 N•m to 0.25 N•m
NOTE
• Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or malfunction due
to damage to the screw or unit.
Ferrule terminal model
2
)
with insulation sleeve
AI 0,34-6TQ
Al 0,5-6WH
D+ D-
V-
Tightening torque
0.3 mm
without insulation sleeve
A 0,34-7
A 0,5-6
<Connection example of multiple inverters>
To next inverter
D+ D-
D+ D-
V-
To master
Cable size
Small
2
2
to 0.75 mm
(Tip thickness: 0.4 mm /tip width: 2.5 mm)
Crimping tool
Manufacturer
name
Phoenix Contact
CRIMPFOX 6
Co., Ltd.
V-
Screwdriver
flat-blade screwdriver
WIRING