Shrm - Toshiba RBC-EXW21E2 Quick Reference

Super digital inverter remote controller
Table of Contents

Advertisement

SHRM

DN
Item
01
Filter sign lighting
time
02
Dirty state of filter
03
Central control
address
04
Specific indoor unit
priority
06
Heating temp shift
0d
Existence of
automatic cool/heat
mode
0F
Cooling only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
19
Flap type
(Adjustment of air
direction)
1E
Temp difference of
automatic cooling/
heating mode
selection COOL →
HEAT, HEAT →COOL
28
Automatic restart of
power failure
29
Operation condition
of humidifier
2A
Selection of option/
error input (CN70)
2E
HA terminal (CN61)
select
30
Automatic elevating
grille
31
Ventilating fan
control
32
TA sensor selection
33
Temperature unit
select
40
Control for humidifier
(+ drain pump control)
5d
High ceiling selection
(Air volume selection)
60
Timer set
(Wired remote
controller)
62
Smudging-proof
control clear
92
Outside interlock
release condition
0000 : None
0002 : 2500H
0004 : 10000H
0000 : Standard
0001 : No.1 unit
to
0099 : Unfixed
0000 : No priority
0000 : No shift
0002 : +2˚C
to
0000 : Provided
0000 : Heat pump
0000 : (1-way air discharge cassette)
0001 : (4-way air discharge cassette) to 0037
0000 : Unfixed
0001 : No.1 unit
to
0001 : No.1 unit
to
0000 : Individual
0002 : Follower unit of group
0000 : Not provided
0004 : [4-way Air Discharge Cassette type] and [Under Ceiling type]
0000 : 0 deg
to
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None
0000 : Usual
(Detection control for heat exchanger temperature)
0000 : Filter input
0002 : Humidifier input
0000 : Usual
0000 : Unavailable
(Standard,
Oil guard panel)
0000 : Unavailable
0000 : Body TA sensor
0000 : ˚C (at factory shipment)
0000 : None
0002 : Humidifier + Ultrasonic system
(Pump ON after specified time passed) (Unused)
0003 : Humidifier + Natural drain system (Pump OFF)
[4-way Air Discharge Cassette type] and [Under Ceiling type]
0000 : Standard filter
0001 : Super-long life
[Concealed Duct Standard type]
0000 : Standard static pressure
(40Pa)
0003 : High static pressure 2
(100Pa)
0000 : Available (Operable)
0000 : Clear
0000 : Operation stop
Description
0001 : 150H
0003 : 5000H
0001 : High degree of dirt
(Half of standard time)
0064 : No.64 unit
0001 : Priority
0001 : +1˚C
0010 : +10˚C
(Up to +6 recommended)
0001 : Not provided
(Automatic selection from
connected outdoor unit)
0001 : Cooling only
(No display of [AUTO] [HEAT])
0001 to 0034
0030 : No.30 unit
0064 : No.64 unit
0001 : Header unit of group
0001 : Swing only
0010 : 10 deg
0001 : Reset
0001 : Condition ignored
0001 : Alarm input (Air washer, etc.)
0001 : Leaving-ON prevention control
0001 : Available
(Auto grille, Oil guard,
Auto grille panel)
0001 : Available
0001 : Remote controller sensor
0001 : ˚F
0001 : Humidifier + Vaporizing system
(Pump ON)
0001 : High static pressure 1
(70Pa)
0005 : Correspond to quiet sound
0006 : Low static pressure (20Pa)
0001 : Unavailable (Operation prohibited)
0001 : Release communication signal
receive
– 39 –
At shipment
According to type
0000 : Standard
0099 : Unfixed
0000 : No priority
0002 : +2˚C
(Floor type 0000: 0˚C)
0001 : Not provided
0000 : Heat pump
According to model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
According to type
0003 : 3 deg
(Ts±1.5)
0000 : None
0000 : Usual
0002 : Humidifier
0000 : Usual
(HA terminal)
0000 : Unavailable
0000 : Unavailable
0000 : Body TA sensor
0000 : ˚C
0003 : Humidifier ON,
Pump OFF
0000 : Standard
0000 : Available
4- way Air Discharge
Cassette type only
0000 : Operation stop