9. Montor Function of Remote Controller Switch
<Produre> (RBC-AMT21E)
1
Push
+
buttons simultaneously for 4 seconds or more to call up the service monitor mode.
2
Pushing
button returns the display to the normal display.
< RBC-AMT21E >
2
1
1
(RBC-AMT31E, RBC-AMT32E)
1
CL
TEST
Push
+
buttons simultaneously for 4 seconds or more to call up the service monitor mode.
The service monitor goes on, and temperature of the item code
2
Push the temperature setup
For displayed codes, refer to the table below.
3
Push
(
RBC-AMT32E) button to change the item to one to be monitored.
UNIT
UNIT LOUVER
Then monitor the indoor unit and sensor temperature or operation status in the corresponding
refrigerant line.
4
TEST
Pushing
button returns the display to the normal display.
CODE
Data name
No.
Room temp.
00
(Under control) (Note 1)
01
Room temp. (Remote controller)
02
Indoor suction temp. (TA)
03
Indoor coil temp. (TCJ)
04
Indoor coil temp. (TC2)
05
Indoor coil temp. (TC1)
08
Indoor PMV opening degree
F2
Indoor fan accumulated operation time
F3
Filter sign time
0A
No. of connected indoor units
0B
Total HP of connected indoor units
0C
No. of connected outdoor units
0D
Total HP of connected outdoor units
(Note 1) In the group connection, only data of the
header indoor unit isdisplayed.
(Note 2) 01: Only compressor 1 is ON.
10: Only compressor 2 is ON.
11: Both compressor 1 and 2 are ON.
(Note 3) For the CODE No., an example of header unit
is described.
< RBC-AMT31E >
UNIT No.
TEMP.
2
TIMER SET
FAN
4
TIME
SWING/FIX
FILTER
RESET TEST
SET CL
UNIT
1
/
buttons to select the CODE NO. (DN code) to be monitored.
Display
CODE
Unit
form
No.
10
˚C
× 1
11
˚C
× 1
12
˚C
× 1
13
˚C
× 1
14
˚C
× 1
15
16
˚C
× 1
17
pls
× 1/10
18
h
× 100
19
h
× 1
1A
unit
1B
HP
× 10
1D
unit
1E
HP
× 10
1F
(Note 4) Upper girder of CODE No. indicates the
– 43 –
< RBC-AMT32E >
CODE No.
TEMP.
ON / OFF
2
MODE
4
VENT
FILTER
RESET
3
1
00 00 00 00 00
is firstly displayed.
Data name
Compressor 1 discharge temp. (Td1)
Compressor 2 discharge temp. (Td2)
High pressure sensor detection pressure (Pd)
Low pressure sensor detection pressure (Ps)
Suction temp. (TS)
Outdoor coil temp. (TE)
Liquid side temp. (TL)
Outside temp. (TO)
Low pressure saturation temp. (TU)
Compressor 1 current (I1)
Compressor 2 current (I2)
PMV1 + 2 opening degree
Compressor 1, 2 ON/OFF
Outdoor fan mode
Outdoor unit HP
outdoor unit No.
1: Header unit (A)
2: Followe run it (B)
3: Follower unit (C)
4: Follower unit (D)
(RBC-AMT32E Not used)
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
VENT
TEST
SET
CL
SWING/FIX
UNIT LOUVER
3
Display
Unit
form
˚C
× 1
˚C
× 1
MPa
× 100
MPa
× 100
˚C
× 1
˚C
× 1
˚C
× 1
˚C
× 1
˚C
× 1
A
× 10
A
× 10
pls
× 1/10
(Note 2)
0 to 31
HP
× 1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rbc-amt32eRbc-amt21eRbc-amt31e43166002431660114316v194