Tools For Installation; Supplied With The Hydran M2-X - GE Hydran M2-X Installation Manual

Transformer gas monitoring system
Hide thumbs Also See for Hydran M2-X:
Table of Contents

Advertisement

circulation and is easily accessible for installation and taking oil samples
directly from the Hydran M2-X.
Location #D: Upper Filling Valve
Most transformers are equipped with an upper filling valve. This location
offers excellent oil circulation, but is not easily accessible and may require an
outage to install the Hydran M2-X.
Location #E: Top of Cooling System
Some transformers may have a valve that is mounted on the pipe that joins
the top tank of the transformer to the top of the cooling system. This location
offers an excellent circulation of oil; but is not easily accessible and may require
an outage to install the Hydran M2-X.

Tools for installation

Supplied with the Hydran M2-X

3/16-in Hex Key with 9-in
Blade & Cushion Grip T- Handle
Roll of PTFE tape
Page 18
84 mm
6 mm
(0.25 in)
Figure 12: Bottom Clearance
1/16-in and 5-32-in
standard Hex (Allen) L-
Keys
Hydran* M2-X Installation Guide
Spanner wrench
MA-028
Rev. 2.1, 11-Jun-20