GE Hydran M2-X Installation Manual page 54

Transformer gas monitoring system
Hide thumbs Also See for Hydran M2-X:
Table of Contents

Advertisement

Communications
Ports
Optional
Communications
Port
Optional I/O Up to 4 of the following to be specified when ordering:
MISCELLANEOUS
Enclosure • Type NEMA 4X
Electronic
Modules
Sensor Heating Heater plate to maintain sensor between 15 and 65 °C (59 and
Oil Temperature • Oil at the valve: -40 to +90 °C (-40 to +194 °F)
Page 54
• Moisture (level and average) and analog High contacts
• Moisture (level and average) and analog High-High contacts
Relay contact maximum switching capacity:
• Resistive load: 50 VA, 60 W (power factor = 1)
Relay contact maximum operating current:
• Resistive load: 3 A (ac/dc)
• One RS-232 port for local laptop computer connection
• One RS-485 port for connection to local Hydran network or
remote communication
1 of the following to be specified when ordering:
• Integrated serial to Ethernet 10/100BaseT; Part Number
17046
• Integrated Fiber Optic Ethernet 100BaseFX, ST Multimode;
Part Number 18321
• Integrated dial-up Modem V.92/56k; Part Number 16868
• General-purpose 4–20 mA analog input; 2,000 V RMS
isolation; Part Number 16528
• Analog 4–20 mA output; 500- maximum loading; 2,000 V
RMS isolation; Part Number 16529
• Dual digital inputs for dry contacts; internal wetting 24 VDC;
2,000 V RMS isolation; Part Number 17464
• Cast aluminum, powder pint, white
• External dimensions: 315 mm long x 219 mm wide x 196 mm
high (12.4 x 8.63 x 7.72 in)
Totally encased CPU and I/O electronics
149 °F) in normal transformer operating conditions to force oil
convection
• Oil at the valve up to 105 °C (221 °F), with optional finned,
high-temperature adaptor, Part Number 18065
Hydran* M2-X Installation Guide
MA-028
Rev. 2.1, 11-Jun-20

Advertisement

Table of Contents
loading

Table of Contents