Mitsubishi Electric GOT1000 Series User Manual page 16

Communication unit for gt15-75j71lp23-z, gt15-75j71br13-z
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

No.
Name
*3
2)
Mode setting switch
*3
3)
Station number setting
switch
Setting of mode (Factory setting at time of shipping: 0)
Mode
Name
On-line
(automatic
0
double line
existent)
1
Use not possible
2
Off-line
3
-
4
-
5
-
6
Test mode 4
7
Test mode 5
8
Test mode 6
9
Test mode 7
A
-
B
-
C
-
D
Test mode 8
E
Test mode 9
F
Test mode 10
Station number setting (factory setting at time of shipping: 1)
<Setting range>
1 to 64
: station number
Other than 1 to 64 : setting error (SW.E LED lamp is lit)
7
Details
Contents
Data link
(automatic double line existent)
Placing local station in parallel
condition
Unusable
Unusable
Unusable
Station-to station test
(Slave station)
Self- loopback test
Internal self- loopback test
Hardware test
Unusable
Unusable
Unusable
Network number confirmation
(LED indication)
Group number confirmation
(LED indication)
Station number confirmation
(LED indication)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gt15 melsecnet/10

Table of Contents