9 Electrical and control settings
Setting of DIP switches and RSW switches
DHW 3-way valve forced ON (All models)
Mirror function (YUTAKI M)
!
C A U T I O N
Never turn all DSW4 dip switch pins ON. If this happens, the software of the unit will be removed.
Never activate "Heater Forced OFF" and "Electric heater or boiler emergency mode" at the same time.

DSW5: Additional setting 3
In the cases where the outdoor unit is installed into a location where its own outdoor ambient temperature sensor can not
give a suitable temperature measurement to the system, it is available the 2nd outdoor ambient temperature sensor as
accessory. By means of DSW1&2 setting, the preferable sensor for each circuit can be selected.
Factory setting
Outdoor unit sensor for circuits 1 and 2.
Outdoor unit sensor for circuit 1; Auxiliary sensor for
circuit 2.
Auxiliary sensor for circuit 1; Outdoor unit sensor for
circuit 2.
Auxiliary sensor instead of outdoor unit sensor for
both circuits.
Use the maximum temperature value between Two3
(boiler / heater thermistor) and Two (water outlet
thermistor) for water control

DSW6: Not used
Factory setting
(Do not change)

DSW7: Additional setting 4
Factory setting
Compatibility with ATW-RTU-04 (When cooling mode
operation is needed)
121
TCGB0123 rev.2 - 10/2019