D.7 - Input Transformer Current For Given Input Voltage; D.8 - Output Transformer Current For Given Output Voltage - Toshiba 4400 Series Installation And Operation Manual

Three phase - 15/20/25/30/50/80/100 kva
Table of Contents

Advertisement

D.7 – Input Transformer Current for Given Input Voltage
TABLE D.7 – INPUT TRANSFORMER CURRENT FOR GIVEN INPUT VOLTAGE
Input
Voltage
208/120V
220/127V
230/133V
240/139V
380/220V
400/227V
415/240V
480/277V
600/347V
D.8 – Output Transformer Current for Given Output Voltage
TABLE D.8 – OUTPUT TRANSFORMER CURRENT AT GIVEN OUTPUT VOLTAGE
Output
Voltage
208/120V
220/127V
230/133V
240/139V
380/220V
400/227V
415/240V
480/277V
600/347V
124
Input Current (Input Currrent + Charging Current) at Full Load (A)
15 kVA
20 kVA
42 (46)
55 (60)
41 (45)
54 (59)
39 (43)
52 (56)
37 (41)
50 (54)
24 (26)
31 (34)
22 (25)
30 (32)
22 (24)
29 (31)
19 (21)
25 (27)
15 (17)
20 (22)
Output Current at Full Load (A)
15 kVA
20 kVA
42
56
39
52
38
50
36
48
23
30
22
29
21
28
18
24
14
19
25 kVA
30 kVA
69 (74)
83 (88)
68 (72)
81 (86)
65 (69)
78 (82)
62 (66)
75 (79)
39 (42)
47 (50)
37 (39)
45 (47)
36 (38)
43 (46)
31 (33A
37 (39)
25 (27)
30 (32)
25 kVA
30 kVA
69
83
66
79
63
75
60
72
38
46
36
43
35
42
30
36
24
29
4400 Series Installation and Operation Manual – 64527-008
50 kVA
80 kVA
139 (148)
222 (238)
136 (144)
217 (232)
130 (138)
207 (222)
124 (132)
199 (213)
78 (84)
126 (134)
75 (79)
119 (128)
72 (77)
115 (123)
62 (66)
99 (106)
50 (53)
80 (85)
50 kVA
80 kVA
139
222
131
210
126
201
120
192
76
122
72
115
70
111
60
96
48
77