Estimated Runtime On Internal Batteries - 50Kva - Toshiba 4400 Series Installation And Operation Manual

Three phase - 15/20/25/30/50/80/100 kva
Table of Contents

Advertisement

Specification
Enclosure
Construction
Color
Emergency Power Off (EPO)
Control Panel
MONITORING
Operator Interface (Front Panel)
Dry Contacts Included
RS-232 Interface
Optional – Intelligent Monitoring
Optional – Remote Status Alarm Panel (RSAP)
ADDITIONAL FEATURES
Optional Matching Battery Cabinets
Optional Matching MBS/PDU Cabinet
OTHER
Warranty (yr.)
Certifications
11.7
Estimated Runtime on Internal Batteries – 50kVA
Below are charts of the estimated runtime for the 4400 Series 50kVA on internal batteries at various loads at a 0.9 and 0.8 Power Factor.
The 80-100kVA UPS is not available with internal batteries. An external battery cabinet (or equivalent) is required to provide backup power.
These runtimes are estimates based on new batteries operating at 76 °F. Actual runtimes may vary due to manufacturing variations, previous discharge
profiles, battery age, and operating temperature.
ESTIMATED RUNTIME ON INTERNAL BATTERIES AT VARIOUS LOADS
UPS
50kVA (0.8 PF)
50kVA (0.9 PF)
1 – Subject to change without notice.
68
4400 SPECIFICATIONS: 50kVA w/ Internal Battery Backup
Estimated Runtime in Minutes at Percent Full Load
10%
20%
30%
>60
>60
>60
>60
>60
>60
Powder Coat, DuPont O'Brien Black
UL 1778, CUL, NEC (NFPS-70), CE, IBC, CBC, ANSI C62.41 (IEEE
587), Nema/PET-1993, OSHA, ISO9000, ISO 14001:2004.
40%
50%
60%
50
37
29
42
32
25
4400 Series Installation and Operation Manual – 64527-008
50kVA
NEMA 1
Welded Steel Chassis
Yes
Touchscreen and LED
Touchscreen and LED
Yes
Yes
Yes – RemotEye 4
Yes
Yes
Yes
3 Years
1
1
70%
80%
90%
24
19
17
19
17
14
100%
14
12