"Serve/Watch" menu

IIn this menu you can call up several parameters for display in order to monitor the pro-
cess. Some of them are shown directly in the menu line, others have to be called up by
entering the item No. Pressing
The following parameters cannot be called up on the communicator:
- Travel counter
- Travel counter limit
- Stroke counter
- Stroke counter limit
- Hysteresis
Use the configuration program on the PC to display or edit these parameters.
The following parameters are not automatically polled/updated:
- Tolerance band
- Shut off value
- Setpoint range
- Alarmmask
Switch the communicator off and on again to display the latest parameter values.
1
Setpoint
Display the setpoint.
2
Position
Display the current position as a percentage of the stroke range.
3
Difference
Display the control deviation as a percentage of the stroke range.
4
Tolerance band
Display the tolerance band as a percentage of the stroke range.
5
Shut off value
Display the shut off value as a percentage of the stroke range.
6
Temperature
Display the temperature in °C.
7
Setpoint range
1
Lower current value
Display the low setpoint range limit.
2
Upper current value
Display the high setpoint range limit.
8
Operating mode
Display the currently active operating mode as a plain text message.
6
(EXIT) will return you to the "Serve/Watch" menu.
F4
"Serve/Watch" menu
"Serve/Watch" menu
42/18-75 EN