ABB CA-16 Instructions Manual
ABB CA-16 Instructions Manual

ABB CA-16 Instructions Manual

Percentage differential relays for bus and transformer protection
Hide thumbs Also See for CA-16:

Advertisement

Quick Links

Effective: September 1995
Supersedes I.L. 41-337.3K, Dated October 1985
( | ) Denotes Changes since previous issue
CONTENTS
This instruction leaflet applies to the following
types of relays:
CA-16 Bus Differential Relay
CA-26 Transformer Differential Relay
The CA-16 relay should not be utilized for trans-
former differential applications since it is too sensi-
tive for overriding the inrush. Likewise the CA-26
relay should not be used for bus protection with
the "four-circuit bus" connections of Figure 8. The
CA-26 relay is suitable for combination bus-trans-
former applications. See "CONNECTIONS".
!
Before putting protective relays into service,
remove all blocking inserted for the purpose
of securing the parts during shipment. Make
sure that all moving parts operate freely.
Inspect the contacts to see that they are clean
and close properly, and operate the relay to
check the settings and electrical connections.
1. APPLICATION
The current transformers should not saturate when
All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the
local ABB Power T&D Company Inc. representative should be contacted.
Courtesy of NationalSwitchgear.com
ABB Automation Inc.
Substation Automation and Protection Division
Coral Springs, FL 33065
CAUTION
Types CA-16 and CA-26
Percentage Differential Relays
for Bus and Transformer
Protection
carrying the maximum external fault current. This
requirement is met if the burden impedance does not
exceed:
(
) R
N
V
I
100
p
pL
ext.
----------------------------------------------------------- - for CA-16 applications
(
)
1.33 I
ext.
(
N
V
I
100
p
cL
ext.
------------------------------------------------------------- - for CA-26 appliations
I
e xt.
where N
= proportion of total ct turns in use.
p
V
= Current transformer accuracy class
cL
C voltage.
I
= maximum external fault current in
ext.
secondary RMS amperes. (let I
100 if max. external fault current is
less than 100A)
R
= current transformer secondary wind-
s
ing resistance, ohms.
For example, if the 400:5 tap of 800:5 C400 current
transformers are used, N
120A, R
= 1.0 ohm the burden should not exceed:
s
(
N
V
I
100
p
cL
ext.
------------------------------------------------------------- - =
(
)
1.33 I
ext.
×
(
0.05
400
120 100
------------------------------------------------------------------------------ -
×
1.33
120
Instruction Leaflet
41-337.3L
s
) R
s
= 400/800 = 0.50, if I
p
) R
s
)
×
1.0
=
1.13 ohms
. =
ext
=
ext.

Advertisement

Table of Contents
loading

Summary of Contents for ABB CA-16

  • Page 1 – ext. ------------------------------------------------------------- - for CA-26 appliations e xt. The CA-16 relay should not be utilized for trans- former differential applications since it is too sensi- tive for overriding the inrush. Likewise the CA-26 where N = proportion of total ct turns in use.
  • Page 2 41-337.3L Courtesy of NationalSwitchgear.com...
  • Page 3 2.2. Operating Circuit ments, and an operating element. For applications where the CA-16 relay is subjected to shock such as The operating circuit consists of an auto-transformer on swinging panels, a sensitive fault detector circuit is and an operating element. The primary of the auto- provided.
  • Page 4 41-337.3L Curve 537956 Figure 6: Typical Time Curves of the CA-16 and CA-26 differential Relays. to the bottom of the guide rod by two small nuts. Its Sub 2 position determines the pick up current of the ele- 187A434 ment.
  • Page 5: Operation

    The same The types CA-16 and CA-26 relays are induction disc relationship applies for the paired coils of the other relays with four electromagnets mounted on two two restraining units of the relay.
  • Page 6 187A425 saturated by the dc component of an asymmetrical Figure 9: External Schematic of the Type CA-16 Relays external fault current. for Protection of a Six Circuit Bus with Three Feeder Groups.
  • Page 7 Figure 10: External Schematic of the Type CA-26 Relay for Transformer Protection and Bus Protection. 4.5. ENERGY REQUIREMENTS 4.6. CONNECTIONS 4.6.1. CA-16 Burden of each restraint coil at 5 amperes To determine the ac connections, identify each pri- VOLT AMPERES POWER FACTOR mary circuit as either a “source”...
  • Page 8: Setting Calculations

    41-337.3L Sub 5 187A426 Figure 11: Diagram of Test Connections for the CA-16 and CA-26 Relays. appreciable if the contribution to an internal fault is supplied principally by only a single circuit. 100 amperes from a single circuit in the four bus circuit...
  • Page 9: Installation

    Sub 2 849A343 The proper adjustments to insure correct operation of Figure 13: Percentage Slope Curve of the CA-16 and CA- this relay have been made at the factory. Upon 26 Relays with Six Restraint Windings in receipt of the relay, no customer adjustments other Series.
  • Page 10 41-337.3L CA-16 relay or 14 amperes to terminals 9 and 19 Position the stationary contact for a minimum of of the CA-26 relay. The contacts should close 1/32 inch wipe. The bridging moving contact when the following operating current is applied to should touch both stationary contacts simulta- the relay with connections of Figure 11.
  • Page 11: Renewal Parts

    Connect the relay per the test circuit of Figure Loosen the lock nut at the top of the element and 11. Pass 20 amperes for the CA-16 and 14 run the core screw down until it is flush with the amperes for the CA-26 relay into terminals 9 and top of the lock nut.
  • Page 12 41-337.3L Courtesy of NationalSwitchgear.com...
  • Page 13 41-337.3L This Space Reserved for Notes Courtesy of NationalSwitchgear.com...
  • Page 14 41-337.3L This Space Reserved for Notes Courtesy of NationalSwitchgear.com...
  • Page 15 41-337.3L This Space Reserved for Notes Courtesy of NationalSwitchgear.com...
  • Page 16 Sub 16 57D7903 Figure 15: Outline and Drilling for the CA-16 and CA-26 Relays in FT-32 Case. ABB Automation Inc. 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL: 954-752-6700 FAX: 954-345-5329 visit our website at www.abbus.com/papd Printed in U.S.A .

This manual is also suitable for:

Ca-26

Table of Contents