Table 3.5 Maximum Permitted Fault Current - Mitsubishi Electric 1100A Series Owner Technical Manual

Uninterruptible power supply system
Table of Contents

Advertisement

CAUTION - Do not open or mutilate the battery or batteries. Released
4.
electrolyte is harmful to the skin and eyes. It may be toxic.
CAUTION - A battery can present a risk of electrical shock and high
5.
short circuit current. The following precautions should be observed
when working on batteries:
a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
e) Disconnect
D) External Battery (10kVA, 20kVA, 30kVA, 40kVA and 50kVA)
Please refer to the following when installing and maintaining batteries:
The customer shall refer to the battery manufacturer's installation
1.
manual for battery installation and maintenance instructions.
The maximum permitted fault current from the remote battery supply
2.
and the DC voltage rating of the battery supply over-current
WARNING
protective device are shown in Table 3.5.

Table 3.5 Maximum Permitted Fault Current

UPS Capacity
(kVA)
E) Installing Air Filter
1. Remove Front Cover
2. Grip the air filter using three ledges
Filter Size: 16W x 4.3H x 0.8D (in)
3. Close the front cover.
1100A SERIES UPS
OWNERS / TECHNICAL MANUAL
charging
disconnecting battery terminals.
DC Voltage
Rating (V)
10
288
20
288
30
288
40
288
50
288
MITSUBISHI ELECTRIC 1100 SERIES UPS
source
prior
to
Maximum Fault
Current Permitted (A)
25,000
25,000
25,000
25,000
25,000
Page Number:
3-6
connecting
or