Table 10 Maximum Permitted Fault Current - Mitsubishi Electric 1100B Series Owner Technical Manual

Table of Contents

Advertisement

D) ▲External Battery (10kVA, 20kVA 30kVA, 40kVA 50kVA, 60kVA, 70kVA and 80kVA)
Please refer to the following when installing and maintaining the batteries:
1.
The customer shall refer to the battery manufacturer's installation manual
for battery installation and maintenance instructions.
2.
The maximum permitted fault current from the remote battery supply and
the DC voltage rating of the battery supply over-current protective device is
WARNING
shown in Table 11.
▲ For other stored energy systems, refer to the supplement.

Table 10 Maximum Permitted Fault Current

UPS Capacity
E)
Installing Air Filter
1. Remove front cover
2. Grip the air filter using three ledges
Filter Size: 16W x 4.3H x 0.8D (in)
3. Close the front cover
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
DC Voltage
(kVA)
Rating (V)
10
288
20
288
30
288
40
288
50
288
60
288
70
288
80
288
MITSUBISHI ELECTRIC 1100B SERIES UPS
Page Number:
Maximum Fault
Current Permitted (A)
25,000
25,000
25,000
25,000
25,000
25,000
25,000
25,000
3-5