WARNING
This UPS does not include an AC input circuit breaker (MCCB) to protect the bypass
and main input circuit. The AC input circuit breaker (MCCB) is to be field supplied
and installed. The recommended circuit breaker (MCCB) specifications are as
follows:
Table 2
Rating of AC Input Circuit Breaker
Capacity (kVA)
10
20
30
40
50
60
70
80
AC input and AC output over current protection and disconnect devices shall be field supplied
and installed. DC output over current protection and disconnect devices shall be field supplied
and installed.
WARNING
This UPS functions with lead acid batteries. If a ▲ is seen, review the
supplemental materials for more information about the stored energy system used.
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
WARNING 4
Input Voltage (VAC)
208
208
208
208
208
208
208
208
WARNING 5
MITSUBISHI ELECTRIC 1100B SERIES UPS
Maximum AC Input
Rating (AAC)
30
60
90
120
150
180
210
240
Page Number:
1-8
Recommended
Breaker (A)
40
80
110
150
225
225
275
300