A Technical Specifications - Huawei DPU40D-N06A3 User Manual

Distributed power system
Hide thumbs Also See for DPU40D-N06A3:
Table of Contents

Advertisement

DPU40D-N06A3, DBU20B-N12A3, and
DBU50B-N12A1 Distributed Power System
User Manual
Table A-1 Environment specifications
Item
Operating
environment
Operating
temperature
Storage
temperature
Operating
humidity
Storage humidity
Altitude
Class C environments refer to sea environments or outdoor land environments (with simple shielding
measures) near pollution sources. If a site is near a pollution source, it is at most 3.7 km away from salt
water, such as the sea and salt lakes, 3 km away from heavy pollution sources, such as smelteries, coal
mines, and thermal power plants, 2 km away from medium pollution sources, such as chemical, rubber,
and galvanization industries, or 1 km away from light pollution sources, such as packing houses,
tanneries, and boiler rooms.
Table A-2 DPU40D-N06A3 specifications
Item
Dimensions (H x
W x D)
Issue 04 (2020-02-29)
A
Technical Specifications
Specifications
Class C
DPU40D-N06A3, DBU20B-N12A3 and DBU50B-N12A1:
With solar radiation: –40° C to +50° C
Without solar radiation: –40° C to +55° C
DPU40D-N06A3: –40° C to +70° C
DBU20B-N12A3 and DBU50B-N12A1: –40° C to +60° C
5%-95% RH (non-condensing)
5%-95% RH (non-condensing)
DPU40D-N06A3, DBU20B-N12A3 and DBU50B-N12A1: –60 m to
4000 m (When the altitude ranges from 2000 m to 4000 m, high
temperature derating applies and the operating temperature decreases
by 1° C for each additional 200 m.)
Specifications
420 mm x 60 mm x 300 mm (excluding the terminal)
Copyright © Huawei Technologies Co., Ltd.

A Technical Specifications

56

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dbu20b-n12a3Dbu50b-n12a1

Table of Contents