2.3. Technical data

Input and output signals
Input and output signal:
Electrical protection:
Short-circuit resistance:
Polarity reversal protection:
Electromagnetic compatibility:
Safety limits:
Display
Type:
Range:
Accuracy:
Digital attenuation:
Display update frequency:
Mechanical resistance:
Vibration
Shock:
Temperature range
Operating ambient temperature:
Storage and transport temperature:
Materials
Display housing:
Miscellaneous
Weight:
Data memory:
Protection category:
METPOINT
UD01
®
4 ... 20 mA (2 conductors)
permanent
No damage, no function
Emitted interference and interference resistance ac-
cording to EN 61326
U
= 28 V, ∑I
= 93 mA, ∑P
i
i
Four-digit red LED display, digit height 7 mm, digit width
4.85 mm
-1999 ... +9999
0.1 % ± 1 digit
0.3 ... 30 s (programmable)
0.0 ... 10 s (programmable)
5 g RMS (20 ... 2000 Hz)
100 g / 11 ms
-25 ... 85 °C
-40 ... 85 °C
PA 6.6, polycarbonate
approx. 100 g
EEPROM, non-volatile
IP 65