Initial steps to run only once
Add the following step(s) to the top pane Initial Steps to Run Only Once section of the prototype job.
Step 1 Add the Enable Bootstrap Mode step.
Step 2 (Optional) If you have MS-E10 devices connected to a secondary port on a JACE, and would like to update the IP
addresses of the station proxies in your NiagaraNetwork, add the Update Connections Using Provisioning Station's DHCP
Server step.
Step 3 (Optional) If you have MS-E10 devices on the same network as the Supervisor (connected to the primary port of a
JACE, or other Supervisor), and would like to update the IP addresses of the station proxies in your NiagaraNetwork, add the
Update Connections Using Niagara Network Discovery step.
Note:
Both of the optional steps match the devices based on the name of the station, or the host id set in the
targetHostId property of the BootstrapExt of the NiagaraStation in the NiagaraNetwork.
Steps to run for each station
Add the following steps to the middle pane (Steps to run for each station) section of the job.
Prerequisites: The Niagara Network Prototype View (for a prototype job) is open.
Note:
The ordering of the steps is important. So, these steps should be added in the order indicated here.
Step 1
Add the Set System Passphrase step, enter the following:
Enter the current passphrase: niagara (the default passphrase for out-of-the-box MS-E10 devices).
Enter the new passphrase you would like to use.
Step 2
Add the Set Platform Credentials step, enter the platform credentials (username / password) that you would like to use.
Step 3
Add the Set Station User Password step, enter the password that you would like to use.
Step 4
Add the Upgrade Out-of-date Software step.
This step has no configuration options.
Step 5
Add the Rename Station step.
This step has no configuration options.
Step 6
Add the Setup Reciprocal Station step and enter the username / password of your Supervisor station.
You can enter the public IP address of your Supervisor station, or leave it blank to have the reciprocal connection auto-detect the
IP address of the Supervisor.
Step 7
Add the Set Time step and do one of the following:
Click the checkbox option to "Use supervisor time" to set the MS-E10 device to the same time as your Supervisor.
Deselect the checkbox and enter a time manually to set the MS-E10 device to another time.
Step 8
Add the Generate Certificate step.
To setup secure communication with the MS-E10 devices, you need to create a self signed certificate for the device. At a
minimum, you need to enter an alias for the certificate, an Organization, and a County Code. The Common Name (CN) should
be left as "<hostname>".
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
MS- E10 User Guide
56

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pbase10

Table of Contents