Advertisement

4 Wiring
[ In the case of PDFY-P20~125VM-A and PDFY-P20~125VM-E ]
1. Pass the white connector (3P:small) of the drain pump
assembly through rubber bushing (A) and the white
connector (3P:Large) through rubber bushing (B).
2. Remove the screws, and then remove the control box cover.
3. Remove the short-circuit connector at CN31 on the
circuit board and insert the white connector
(3P:small) of the drain pump assembly.
4. Insert the white connector(Large) on one of the
leads of the drain pump assembly into the white
relay connector at the side of the control box.
5. If there is slack in the leads, bind them with the clip
on the control box.
Circuit board
Cover
Cover securing screw
(2 places)
Circuit board
White connector
CN29
(3P:small)
<Front view>
4
White Connector (small)
White Connector
(Large)
Rubber bushing
(B)
Rubber bushing
(A)
CN31
Exchange
Short-circuit
connector
<Side view>