Download Print this page

Mitsubishi Electric PAC-KD02DM-FA Installation Manual page 6

Drain water lift-up kit

Advertisement

4. Connect the wires as shown in the figures below.
Procedures
Warning: Perform the following procedures with the power being turned off.
i. Remove the short-circuit connector on CN31.
* In the case of PDFY-10,16, 24, 32 NMU-A and PDFY-P06, P08, P12, P15, P18, P24, P27,P30NMU-E also
remove the yellow connector on the DSA board.
ii. Connect the drain sensor wire to CN31.
iii. Fix the fuse holder (item A ) with the PTT screw (item C ) to the control box, and attach the fuse (item B ).
iv. Connect wire assembly (items 8 or 9 ).
Note. Item 9 (wire) is intended for PDFY-40, 48 NMU-A and PDFY-P36, P48NMU-E. Do not use it for other types.
v . Connect wire assembly (item @) to CNP12.
vi. Connect the drain pump connector to wire assembly (item @).
PDFY-10, 16, 24, 32NMU-A
PDFY-P06, P08, P12, P15, P18, P24, P27, P30NMU-E
ii
Connect to
CN31
i
Remove
Short-circuit
connector
Remove
Connector for
DSA board
Yellow
From
drain sensor
PDFY-40, 48NMU-A
PDFY-P36, P48NMU-E
i
Remove
Short-circuit
connector
ii
Connect to
CN31
From
drain sensor
5. If there is slack in the leads, bind them with the clip on the control box.
DSA board
MA Remo.Con.
CAUTION
Never connect
1
2
Power source
M1
M2 S
W896247H01
Transmission.
Power source
M-NET Remo.Con.
W893038H01
L1
L2
G
iv
8 WIRING
ASSY. A1
MA Remo.Con.
CAUTION
Never connect
1
2
Power source
M1
M2 S
W896247H01
Transmission.
Power source
M-NET Remo.Con.
W893038H01
L1
L2
G
iv
9 WIRING
ASSY. A2
6
Blue
White
iii
AFUSE
HOLDER
CPTT SCREW
3.5X10
B FUSE
Blue
iii
AFUSE
HOLDER
CPTT SCREW
3.5X10
BFUSE
v
@ WIRING ASSY. B
vi
Drain pump
connector
v
@ WIRING ASSY. B
vi
Drain pump
connector

Advertisement