TZIDC DIGITAL POSITIONER | CI/TZIDC/ATEX/IECEX-EN REV. C
A TZIDC Control Unit with TZIDC Remote Sensor*
In this version, the components are supplied in two housings,
which together form one harmonized unit.
The following points should be observed during installation:
Housing 1 (TZIDC Control Unit) contains the electronics
and pneumatics and is mounted separately from the
actuator.
Housing 2 (TZIDC Remote Sensor) contains the position
sensor and is mounted on the linear and rotary actuator.
Perform mechanical mounting as described in Mechanical
mounting on page 13.
The electrical connection is performed as described in
Connection on device - TZIDC Control Unit for remote
position sensor on page 26.
Note
To connect the TZIDC Remote Sensor, a cable with the following
specifications needs to be used:
3-wire, cross-section 0.5 to 1.0 mm
shielded, with at least 85 % coverage
Temperature range up to at least 100 °C (212 °F)
The cable glands must also be approved for a temperature range
up to at least 100 °C (212 °F). The cable glands require a
mounting for the shielding and strain relief for the cable in
addition.
ABB optionally offers a cable gland and cable for the
TZIDC Remote Version.
*
The TZIDC Remote Version is temporarily not available for the marine
version.
B TZIDC Control Unit for remote position sensor
In this version the positioner is supplied without a position
sensor.
The following points should be observed during installation:
Housing 1 (TZIDC Control Unit) contains the electronics
and pneumatics and is mounted separately from the
actuator.
The remote position sensor is mounted on the linear and
rotary actuator. Follow the operating instructions for the
remote position sensor for mechanical mounting!
The electrical connection is performed as described in
Connection on device - TZIDC Control Unit for remote
position sensor on page 26.

Mechanical mounting

General

Figure 4: Operating range
²
Arrow
must move between the arrow marks
1 Measuring range
Figure 5: Measuring and operating ranges of the positioner
Operating range for linear actuators:
The operating range for linear actuators is ±45° symmetrically to
the longitudinal axis. The usable span within the operating range
is at least 25° (recommended figure 40°). The usable span does
not necessarily need to run symmetrically to the longitudinal
axis.
on the device feedback shaft (position feedback point)
1
.
2
2 Operating range
13