8. CAPACITY TABLES
3. Power input of outdoor unit
<Cooling>
(1) Rated power input of outdoor unit
(2) Calculation of the average indoor temperature power input coefficient
Coefficient of the outdoor unit for indoor unit 1 (Outdoor temp. 37 °CD.B., Indoor temp. 20 °CW.B.)
Coefficient of the outdoor unit for indoor unit 2 (Outdoor temp. 37 °CD.B., Indoor temp. 17.8 °CW.B.)
Average indoor temp. power input coefficient (
= 1.09 × 36/(36 + 36) + 1.03 × 36/(36 + 36)
= 1.06
(3) No need to consider Coefficient of the partial load (CTi/CTo)
(4) Outdoor power input (PIo)
Maximum System Capacity (CTx) = Total Outdoor unit Capacity (CTo), so use the following formula
PIo = Outdoor unit Cooling Rated Power Input × Correction Coefficient of Indoor temperature
=4.55 × 1.06
= 4.82 kW
MEES19K180
n
c
)
×
= ∑ {c
(M
k
ave
k=1
n: Total number of the indoor units
k: Number of the indoor unit
c
: Outdoor unit power input coefficient of k indoor unit room temp.
k
M
: Number part of the k indoor unit model (e.g. P36 → 36)
k
4.55 kW (Nominal)
1.09
1.03
n
/ ∑ M
)}
k
k
k=1
-
Hyper Heating Inverter R2-Series
34