Safety controller
Hide thumbs Also See for VItal 1:

Advertisement

Quick Links

Safety controller
Vital
Vital is based on a single channel safety concept where multi-
ple safety sensors can be connected in series and monitored
with a single safety controller. A dynamic signal is sent from
Vital through all connected sensors, and then returned to Vital
which then evaluates the received signal. As each safety sen-
sor inverts the signal, it is possible to detect short circuits or
faults in any of the sensors. Vital 2 and Vital 3 are designed
for use with ABB Jokab Eden sensors, Tina components and
Spot light grids or similar products. Vital 2 and 3 are both
safety controllers with two safe input functions and two output
groups, the only difference between the two models being in
the input configuration.
5:6
Approvals:
TÜV Nord – Vital 1
TÜV Rheinland – Vital 2 and 3
Control of:
Entire safety system based on
the dynamic safety circuit.
Features:
Easy installation
Flexible
Cost effective
Display for troubleshooting
(Vital 2 and 3)
A wide range of safety sen-
sors can be connected into the
circuit
Several safe outputs
Information output
Outputs with time delay
(Vital 2 and 3)
ABB

Advertisement

loading

Summary of Contents for ABB VItal 1

  • Page 1 Vital 2 and Vital 3 are designed for use with ABB Jokab Eden sensors, Tina components and Spot light grids or similar products. Vital 2 and 3 are both...
  • Page 2 Vital 1 Safety controller Dynamic circuit 1 • Up to 30 sensors can be connected to the same dynamic safety circuit Vital 2 Safety controller • Two safety circuits are monitored by one module Dynamic Dynamic • Simple system with...
  • Page 3 +24V +24V Vital 1 Vital 1 The Vital 1 has two (2 NO) safety outputs. Vital 1 has a switching relay output for In DIP switch position 2 (the purpose of In order to protect the output contacts information. The function is determined by...
  • Page 4 Relay information output Technical data – Vital 1 (changeover contact) Manufacturer ABB AB/Jokab Safety, Sweden Indicates Vital is not reset –(0V) +(24V) Indicates Vital is reset Article number/Ordering data: 200 mA (Internal automatic fuse) Max. load on Y14 Vital 1...
  • Page 5 Connection of units and cable lengths to Vital 1 5:10...
  • Page 6 According to PL e (EN ISO 13849-1), connection of sen- units (= 3 x 8 connected to Tina 8A + 3 Tina 8A) can be con- nected to one Vital 1 with a total cable length of 600 metres sors/adaptor units in the Vital safety circuit must be made (0.75 mm...
  • Page 7 Vital 2 is a safety controller that combines functionality with Input function 1: A dynamic safety circuit where ABB Jokab Safety's safety the quick and easy installation of safety sensors. With two sensors such as Eden, Tina and Spot can easily be con- safe input functions and two different output groups, Vital 2 nected in series.
  • Page 8 Operating mode M1 - Separate function Vital 2 Input function 1 controls output group 1, and input function 2 controls output group 2. Operating mode M2 - Input 1, master function Vital 2 Input function 1 stops all outputs, and input function 2 stops output group 2.
  • Page 9 Connection of protection/sensors - Vital 2 Depending on the input function and the Input function 1: Input function 2: number of sensors connected to the safety circuit (odd or even number), the dynamic signal is connected between different ter- minals; A dynamic signal is transmitted from T1, and A dynamic signal is transmitted from T11, depending on the number of sensors in the...
  • Page 10 Technical data – Vital 2 Relay outputs Number of outputs 2 NO Manufacturer ABB AB/Jokab Safety, Sweden Max. load capacity, res. load 6A/250 VAC Max. load capacity, ind. load AC-1: 250 V/1,5 A Article number/ AC-15: 250 V/1,5 A Ordering data DC-1: 50 V/1,5 A...
  • Page 11 With two A two-channel safety circuit designed for opening contacts, e.g. two-channel emergency stop or ABB Jokab  Safety's safe input functions and two different output groups, Vital 3 safety switch JSNY5. One channel is fed with the dynamic...
  • Page 12 Operating mode M1 - Separate function Vital 3 Input function 1 controls output group 1, and input function 2 controls output group 2. Operating mode M2 - Input 1, master function Vital 3 Input function 1 stops all outputs, and input function 2 stops output group 2.
  • Page 13 Connection of protection/sensors - Vital 3 Depending on the input function and the Input function 1: Input function 2: number of sensors connected to the safety loop (odd or even number), the dynamic signal is connected between different ter- minals; One of the two opening contacts is con- A dynamic signal is transmitted from T11, nected between T1 and S1 (dynamic sig-...
  • Page 14 Technical data – Vital 3 Relay outputs Number of outputs 2 NO Manufacturer ABB AB/Jokab Safety, Sweden Max. load capacity, res. load 6A/250 VAC Max. load capacity, ind. load AC-1: 250 V/1,5 A Article number/ AC-15: 250 V/1,5 A Ordering data DC-1: 50 V/1,5 A...