Connection of Power cables/Earth wires/
2
Signal wires
Connection diagram
The shield earth of the RS-485
signal wires should be single-point
earth. Earth the wires on the Touch
Screen Controller.
Set the Digital Input/Output Relay
Interface address with SW1. Assign
1 to 4 to each address to avoid
duplication. You can set the digital
Input/Output Relay Interface address
independently from the TCC-LINK
Relay Interface address or the
Energy Monitoring Relay Interface
address.
CAUTION: The SW1 setting is read
when the power is turned on. Push
the reset switch (SW7) after
changing the address.
CAUTION: Set the RS-485
terminator resistor on the TCS-NET
Relay Interface. No terminator
resistor setting switch is provided
on the Digital Input/Output Relay
Interface.
(continued)
Connect the
shield wire of the
two wires
ADDRESS
DIGITAL I/O
INTERFACE
ADDRESS
DIGITAL I/O
INTERFACE
TCS-NET RELAY
INTERFACE
SW1
DI 1
4
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
DO1
DO2
DO3
DO4
GND
+12V
SW1
DI 1
1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
DO1
DO2
DO3
DO4
GND
+12V
7
Input contact 1
Input contact 2
Input contact 3
Input contact 4
Input contact 5
Input contact 6
Input contact 7
Input contact 8
The RS-485 signal wire has
polarity A and B. Be careful when
connecting the wire.
Load 1
Load 2
Load 3
Load 4
Input contact 1
Input contact 2
Input contact 3
Input contact 4
Input contact 5
Input contact 6
Input contact 7
Input contact 8
Load 1
Load 2
Load 3
Load 4