1MRS 751055-MUM Directional or Non-Directional REJ 527 Earth-Fault Relay Issued: 07.07.99 Version: A/17.04.2001 Checked: H.S. Operator’s Manual Approved: L.N. We reserve the right to change data without prior notice. Contents 1. Introduction ................6 1.1. About this manual ................6 1.2. The use of the relay ...............6 1.3.
Page 4
REJ 527 Directional or Non-Directional Earth-Fault Relay 1MRS 751055-MUM Operator’s Manual 3.3.3. Protection indications ............23 3.3.4. I/O test ................23 3.3.5. Green indication LED ............24 3.3.6. Yellow indication LED ............24 3.3.7. Red indication LED ............25 4. Technical Description ............. 26 5.
The purpose of this manual is to provide the user with the basic information on the relay REJ 527 and to focus on detailed instructions for using the Man-Machine Interface (MMI) of the relay. In addition to the instructive part, the manual includes a short chapter discussing the service of the relay.
• MMI with an alphanumeric LCD and manoeuvring buttons • User-selectable password protection for MMI • Display of primary current and voltage values as well as phase angle values 1.4. Guarantee Please inquire the guarantee of your nearest ABB representative.
Directional or Non-Directional Earth-Fault Relay REJ 527 1MRS 751055-MUM Operator’s Manual Safety Information Dangerous voltages can occur on the connectors, even though the auxiliary voltage is disconnected. National and local electrical safety regulations must always be fol- lowed. The frame of the protection relay has to be carefully earthed.
REJ 527 Directional or Non-Directional Earth-Fault Relay 1MRS 751055-MUM Operator’s Manual Instructions 3.1. MMI features 3.1.1. Front panel The front panel of the protection relay includes: • an alphanumeric LCD display for 2 x 16 characters • three indication LEDs (ready, start, trip) •...
Operator’s Manual 3.1.2. Display 3.1.2.1. Display idle mode Self-supervision tests are run during initialisation. After all tests are completed, the display will return to idle mode showing the text ABB. READY START TRIP )LJ 'LVSOD\ LQ LGOH PRGH 3.1.2.2.
REJ 527 Directional or Non-Directional Earth-Fault Relay 1MRS 751055-MUM Operator’s Manual 3.1.2.4. How to adjust display contrast Contrast of the display is automatically adjusted depending on the ambient temper- ature. To obtain optimum readability, the contrast can be adjusted manually. To change the contrast, the LCD display must be in idle mode.
Directional or Non-Directional Earth-Fault Relay REJ 527 1MRS 751055-MUM Operator’s Manual Table 3.1.3-1 Button navigation Desired step or operation Push-button Action ↓ Step downward in the main menu or a submenu ↑ Step upward in the main menu or a submenu →...
REJ 527 Directional or Non-Directional Earth-Fault Relay 1MRS 751055-MUM Operator’s Manual 4. Press the [E] button and the second row starts to flash indicating that it is allowed to set language. 5. Move to the desired language and confirm the selection by pressing the [E] but- ton.
Directional or Non-Directional Earth-Fault Relay REJ 527 1MRS 751055-MUM Operator’s Manual → ← • To enter a submenu, press the [ ] button; to exit press the [ ] button. • Press the [C] button to return to idle mode.
REJ 527 Directional or Non-Directional Earth-Fault Relay 1MRS 751055-MUM Operator’s Manual • MEASUREMENTS = monitors measured values • RECORDED DATA = saved alarm event values from protection stages • INFO = information on the relay, e.g. relay name, serial number Data of every menu group on the user level can be monitored without a password.
Directional or Non-Directional Earth-Fault Relay REJ 527 1MRS 751055-MUM Operator’s Manual Main Menu Parameter Menu Group Menu MEASUREMENTS RECORDED DATA RECORDED DATA RECORDED DATA 1. Uo :x.xx% 1. EVENT 1. Io :x.xx% 2. EVENT : ± x.xx% 3. EVENT 1.Iϕ...
REJ 527 Directional or Non-Directional Earth-Fault Relay 1MRS 751055-MUM Operator’s Manual READY START TRIP ALARM Io> Iob & Uo )LJ $ODUP The non-latching operation mode selected, the operation indication disappears along with the fault. When the indication is selected to be latching, it remains even if the fault disappears.
REJ 527 Directional or Non-Directional Earth-Fault Relay 1MRS 751055-MUM Operator’s Manual • CONFIGURATION 3.2.4.2. How to change settings Actual settings are found in the first submenu, and they are not editable. Actual settings consist of settings either of group 1 or 2, depending on which of these are selected to be active.
Directional or Non-Directional Earth-Fault Relay REJ 527 1MRS 751055-MUM Operator’s Manual the password. If the default password “999” is still valid, no password is required. 4. The first digit or character of the setting value/text of the concerned parameter →...
REJ 527 Directional or Non-Directional Earth-Fault Relay 1MRS 751055-MUM Operator’s Manual 5. To exit the setting mode without saving changes, press the [C] button once before confirming and the display returns to view mode. Press the [C] button once more and the display returns to idle mode.
Directional or Non-Directional Earth-Fault Relay REJ 527 1MRS 751055-MUM Operator’s Manual 3.2.5. Menu chart - Default station name - Note: ABB is the default MEASUREMENTS MEASUREMENTS MEASUREMENTS :x.xx% V:x.xx :x.xx% A:x.xx :±x.xx% A:±x.xx :±x.xx° RECORDED DATA RECORDED DATA RECORDED DATA 1.
REJ 527 Directional or Non-Directional Earth-Fault Relay 1MRS 751055-MUM Operator’s Manual • A text message and LED indication. This type of message is related to an internal fault or an alarm message. 3.3.2. Priority of indication messages The messages on the LCD have a certain priority order. If different types of indications are activated simultaneously, the message with the highest priority appears on the display.
Directional or Non-Directional Earth-Fault Relay REJ 527 1MRS 751055-MUM Operator’s Manual 3.3.5. Green indication LED READY START TRIP )LJ *UHHQ LQGLFDWLRQ /(' Two different functions are embedded in the READY indicator: power on and IRF (internal relay fault). • Indicator off: •...
Operator’s Manual Technical Description REJ 527 is designed to be used as a stand-alone protection relay in medium voltage distribution systems where the relay can be applied as the main or backup protection relay of an object. The whole function software used in the relay is preloaded into program memory in production stage.
Please contact the manufacturer or the nearest representative for further information about checking, overhaul and recalibration of the relay. When contacting ABB for ordering service, please state the possible fault code. Note! Static protection relays are measuring instruments that should be handled with care and protected against moisture and mechanical stress, especially during transport.
Page 27
Directional or Non-Directional Earth-Fault Relay REJ 527 1MRS 751055-MUM Operator’s Manual Danger! Do not open the secondary circuit of a current transformer under any phases of the testing if the primary circuit is live. The high voltage generated by an open CT secondary circuit could be lethal and may damage instruments and insulation.
REJ 527 Directional or Non-Directional Earth-Fault Relay 1MRS 751055-MUM Operator’s Manual When the test circuit has been completed and the switchgroups set, the auxiliary voltage may be connected to the relay. The operation of the test circuit can be verified with the aid of a multimeter.
Directional or Non-Directional Earth-Fault Relay REJ 527 1MRS 751055-MUM Operator’s Manual SGR2 = 1 > to PO1 SGR3 = 8 >> to SO2 SGR4 = 2 >> to PO2 SGF2 = 128 deblocking not in use SGF3 = 5 non-directional Setting values can be those actual used.
REJ 527 Directional or Non-Directional Earth-Fault Relay 1MRS 751055-MUM Operator’s Manual Customer Feedback Date: To fax: +358 10 224 1094 Category: Comment Query Complaint In case of feedback related to a specific product, please state the name of the product.