Installation; Installation Of Ahu Kit; Mah2/Pah2 Generation - Panasonic PAW-160MAH2L Installation Instructions Manual

Air handling unit kit
Table of Contents

Advertisement

4

Installation

4.1

Installation of AHU Kit

WARNING
Electric shock from live power supply cords
Electric shock may result from contact with live power supply cords.
► Wiring installation must only be performed by a qualified electrician.
► Before starting to work on any machines or devices, always switch off the power supply
and lock it in switched-off position.
ATTENTION
!
Damage to the AHU Kit enclosure and to the thermistor and/or expansion valve wires
Exposing the AHU Kit enclosure to direct sunlight can cause overheating and material damage and
should therefore be avoided.
Exposing the wires of thermistors or, in case of the ECOi and ECO G systems, of the expansion
valve to the outside and/or to direct sunlight might damage the wires and should therefore be
avoided.
► Attach the AHU Kit either directly to the Air Handling Unit or to a wall nearby and make
sure that it is not exposed to direct sunlight.
► Use protecting wire ducts to avoid exposing the wires of thermistors and the electronic
expansion valve to the outside.

4.1.1 MAH2/PAH2 generation

Mount the MAH2/PAH2 generation AHU Kit according to the following instructions. Please note that
screws and other fixing materials, which may be required, are not included in the kit.
1. Choose an installation location observing the minimum allowed distances to any adjacent
objects on all sides of the enclosure as shown below (left).
2. Prepare the 4 holes at the installation location, using the dimensions as shown below (right).
The distance between the centre points of the holes must be 254 mm.
Left:
min.
50 mm
Front:
min. 200 mm
AHU Kit – Installation Instructions – 09/2021
Above: min. 50 mm
Right:
min.
50 mm
Below: min. 100 mm
Installation
254
47
4