13. Other Functions

13-1. Maintenance function for power supply stop of indoor unit. (E06 ignore)
The system can continue operation even if outdoor unit cannot communicate with some indoor units.
It is necessary to set to EEPROM the allowed number of operating indoor units not to be able to communicate.
When the set value is 0 or more, the system continues operating even if it is not possible to communicate with the
stopped indoor units
However, allowed number of indoor units to be able to communicate is fixed to 75% of number of indoor units
after the power supply of the outdoor unit.
* If 75% of the number of indoor units is decimal number, round up.
EEPROM setting in main outdoor unit
CODE: 23
Setting No
Allowed number of missing indoor unit
-1
0
1
2
62
63
Examples :
In case of 10 outdoor units, setting No. becomes "3".
Normal operation
ON
ON
ON
ON
ON
ON
After power supply of outdoor unit
OFF
OFF
OFF
OFF
This function is invalid
(factory preset mode)
0
1
2
Interval of "1"
62
63
Operation continue: Indoor unit failure=3
ON
ON
ON
Error occurs: Indoor unit failure=4 > Setting No "3"
ON
ON
ON
Operation continue: Stopped units does not count
ON
ON
ON
No error: Normal indoor unit =8
OFF
OFF
OFF
Error occurs: Normal indoor unit =7 < 10 * 0.75
OFF
OFF
OFF
Control Functions-Outdoor Unit
OFF
OFF
OFF
OFF
OFF
OFF
10 * 0.75
OFF
OFF
OFF
OFF
1 - 39
2WAY SYSTEM
Setting No "3"
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1